C h a p t e r 4 O p e r a t i o n s
4 - 5
4_
4.1.4 General Setting (Input Group)
4.1.4.1 Current Transformer primary ampere (CT Pri)
Ampere of Hall sensor primary side, can be set range is 1~9999 A. The default value is 50 A.
Steps of setup are as follows:
1.
Press ENTER on the parameter page and start setting after the number flashes.
2.
Press UP or DOWN to select the numeric.
3.
Press LEFT key move to next digit.
4.
Repeat step 2 to 3 until finishing ampere setting, press ENTER key to save and return to the menu.
※
Press LEFT key and hold 2 seconds to cancel input and return to the previous menu.
4.1.4.2 Current Unit (I unt)
Current unit setting can select is 0.001A
、
0.01A
、
0.1A
、
1A. The default value is 0.01A.
Steps of setup are as follows:
1.
Press the ENTER key on the parameter page, the setting starts after the content flashes.
2.
Use UP and DOWN to select current unit.
3.
Press ENTER key to finish setting and back to next parameter page.
※
Press LEFT key and hold 2 seconds to cancel input and return to the previous menu.
4.1.4.3 Power Unit (W unt)
Power unit setting can select is 0.1W
、
1W
、
0.01kW
、
0.1kW
、
1kW
、
0.01MW
、
0.1MW
、
1MW. The default value is
0.01kW.