D e lt a M u lt i- C ir c u i t P o w e r M e t e r D P M - M A11 2 1 U s e r M a n u a l
4 - 1 2
4
4.3.1 Data Log Function Setting
The data logging function can set the parameters to be recorded according to required, up to 21 parameters can be set.
There are 21 parameters to choose, see Table 4-1
Table 4-1
NO.
Parameter
NO.
Parameter
NO.
Parameter
NO.
Parameter
NO.
Parameter
0
NONE
1
Voltage
2
Loop 1
current
3
Loop 2
current
4
Loop 3
current
5
Loop 4
current
6
Loop 5
current
7
Loop 1
power
8
Loop 2
power
9
Loop 3
power
10
Loop 4
power
11
Loop 5
power
12
Loop 1
positive
energy
13
Loop 2
positive
energy
14
Loop 3
positive
energy
15
Loop 4
positive
energy
16
Loop 5
positive
energy
17
Loop 1
negative
energy
18
Loop 2
negative
energy
19
Loop 3
negative
energy
20
Loop 4
negative
energy
21
Loop 5
negative
energy
The time parameters required for the data logging function are as Table 4-2
Table 4-2
MODBUS
Address
Item
Range
Data
Type
Unit
BYTE
Read(R)/
Write(W)
Hex
Modicom
Format
210
400529
Parameter assign
0: All parameters
1: Assign parameter
word
2
R / W
211
400530
Logging interval time
1~32767
word
2
R / W
212
400531
Unit of interval time
0: Second
1: Minute
2: Hour
3: Day
word
2
R / W
213
400532
Date and time for start
2010~2099
word
Year
2
R / W
214
400533
1~12
word
Month
2
R / W
215
400534
1~31
word
Day
2
R / W
216
400535
0~23
word
Hour
2
R / W
217
400536
0~59
word
Minute
2
R / W
218
400537
0~59
word
Second
2
R / W
219
400538
Date and time for stop
2010~2099
word
Year
2
R / W
21A
400539
1~12
word
Month
2
R / W
21B
400540
1~31
word
Day
2
R / W
21C
400541
0~23
word
Hour
2
R / W