Chapter 5 Parameters and Functions
5-11
_5
6D
40110
Pickup setpoint (total
apparent power value
exceeding this value
triggers alarm)
0.000 – 99999.999
float kVA
4
R/W
6E
40111
6F
40112
Pickup time delay
(alarm–trigger delay) 0 – 99
word
s
2
R/W
70
40113 Dropout setpoint (total
apparent power value
below this value
clears alarm)
0.000 – 99999.999
float kVA
4
R/W
71
40114
72
40115
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W
Alarm – Lead PF
73
40116 Alarm enable
0: Disable
1: Enable
word
2
R/W
74
40117
Pickup setpoint (total
power factor value
below this value
triggers alarm)
0.00000 – 1.00000
float
4
R/W
75
40118
76
40119
Pickup time delay
(alarm–trigger delay) 0 – 99
word
s
2
R/W
77
40120
Dropout setpoint
(total power factor
value exceeding this
value clears alarm)
0.00000 – 1.00000
float
4
R/W
78
40121
79
40122
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W
Alarm – Lag PF
7A
40123 Alarm enable
0: Disable
1: Enable
word
2
R/W
Summary of Contents for DPM-D520I
Page 3: ......
Page 9: ...Delta Din rail Power Meter DPM D520I User Manual 1 4 _1 _1 MEMO...
Page 15: ...Delta Din rail Power Meter DPM D520I User Manual 2 6 _2 MEMO...
Page 31: ...Delta Din rail Power Meter DPM D520I User Manual 4 10 _4 MEMO...
Page 116: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Error Codes 6 2 6 2 Alarm Types 6 2 6...
Page 119: ...Delta Din rail Power Meter DPM D520I User Manual 6 4 _6 Memo...
Page 125: ...Delta Din rail Power Meter DPM D520I User Manual A 6 _A _1 _1 MEMO...