Alarm – Over Active Power Demand
96
40151 Alarm enable
0: Disable
1: Enable
word
2
R/W
97
40152
Pickup setpoint
(active power demand
value exceeding this
value triggers alarm)
0.000 – 99999.999
float
kW
4
R/W
98
40153
99
40154
Pickup time delay
(alarm–trigger delay) 0 – 99
word
s
2
R/W
9A
40155
Dropout setpoint
(active power demand
value below this value
clears alarm)
0.000 – 99999.999
float
kW
4
R/W
9B
40156
9C
40157
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W
Alarm – Over Reactive Power Demand
9D
40158 Alarm enable
0: Disable
1: Enable
word
2
R/W
9E
40159
Pickup setpoint
(reactive power
demand value
exceeding this value
triggers alarm)
0.000 – 99999.999
float
kW
4
R/W
9F
40160
A0
40161
Pickup time delay
(alarm–trigger delay) 0 – 99
word
s
2
R/W
A1
40162
Dropout setpoint
(reactive power
0.000 – 99999.999
float
kW
4
R/W
Summary of Contents for DPM-D520I
Page 3: ......
Page 9: ...Delta Din rail Power Meter DPM D520I User Manual 1 4 _1 _1 MEMO...
Page 15: ...Delta Din rail Power Meter DPM D520I User Manual 2 6 _2 MEMO...
Page 31: ...Delta Din rail Power Meter DPM D520I User Manual 4 10 _4 MEMO...
Page 116: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Error Codes 6 2 6 2 Alarm Types 6 2 6...
Page 119: ...Delta Din rail Power Meter DPM D520I User Manual 6 4 _6 Memo...
Page 125: ...Delta Din rail Power Meter DPM D520I User Manual A 6 _A _1 _1 MEMO...