Chapter 4 Operation
4-5
4_
Secondary-side potential transformer (PT2):
Voltage for the secondary-side potential transformer, with a selectable range of 1~9999 V (factory default:
1 V). Corresponding Modbus address 0x11
4.2.4
Set up the System Parameters
Wiring (Power System):
Options are one-phase two-wire (1PH2W), one-phase three-wire (1PH3W),
three-phase three-wire (3PH3W), and three-phase four-wire (3PH4W; default). Corresponding Modbus
address is 0XD.
Rotation (Phase):
Options are ABC mode (default) and CBA mode. When the phase A wiring is
connected to the meters phase C and phase C wiring is connected to the meter’s phase A, you can use
CBA mode without having to reconnect the wiring. Corresponding Modbus address is 0XC.
Number CT:
The number of CTs on the system; options are 0, 1, 2 and 3 (default). Corresponding
Modbus address 0X12.
Number PT:
The number of PTs on the system; options are 0, 2 and 3 (default).
Corresponding Modbus
address 0X12.
*Note:
When the wiring is one-phase two-wire (1PH2W), the fixed number of CT and PT is 1 and 3. When the
wiring is one-phase three-wire (1PH3W), the fixed number of CT and PT is 2 and 3, which are not able to be
modified.
4.2.5
Set up the Alarms
Alarm:
Whether this alarm is enabled or disabled (factory default).
Pickup Setpoint:
When the threshold (default: 0) set on the meter is exceeded, an alarm is generated
triggered.
Pickup Time Delay:
When the threshold set on the meter is exceed for a period longer than the pickup
time delay (default: 0), the alarm is triggered.
Dropout Setpoint:
When the threshold (default: 0) set on the meter falls short, the alarm is cleared.
Dropout Time Delay:
When the measurement value falls below the threshold for a period longer than
the dropout time delay (default: 0), the alarm is triggered.
The corresponding MODBUS address for alarms would be 0x1F~0xDD.
Summary of Contents for DPM-D520I
Page 3: ......
Page 9: ...Delta Din rail Power Meter DPM D520I User Manual 1 4 _1 _1 MEMO...
Page 15: ...Delta Din rail Power Meter DPM D520I User Manual 2 6 _2 MEMO...
Page 31: ...Delta Din rail Power Meter DPM D520I User Manual 4 10 _4 MEMO...
Page 116: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Error Codes 6 2 6 2 Alarm Types 6 2 6...
Page 119: ...Delta Din rail Power Meter DPM D520I User Manual 6 4 _6 Memo...
Page 125: ...Delta Din rail Power Meter DPM D520I User Manual A 6 _A _1 _1 MEMO...