Delta Din-rail Power Meter DPM-D520I User Manual
2-2
_2
2.1
Electrical Characteristic
Input
Voltage Connection
1PH2W, 1 CT
1PH3W, 2 CT
1PH3W, No CT
1PH3W, No CT
3PH3W, Δ connection, 3 CT, 2 PT
3PH4W, Y connection, 3 CT, No PT
3PH3W, Δ connection
, 3 CT, No PT
3PH4W, Y connection, 3 CT, 3 PT
3PH3W, Δ connection, 2 CT, No PT
3PH4W, Y connection, 2 CT, 3 PT
3PH3W, Δ connection, N
o CT
3PH4W, Y connection, No CT
Rated Voltage
Line voltage: 35–690 VAC (L-L)
Phase voltage: 20–400 VAC (L-N)
Rated Current
63 A
Measure Current
20mA to 63A
Start Current
20mA
Frequency
50/60 Hz
Harmonic Distortion
for Individual
Current/Voltage
31
Voltage Input
Measuring Category: CAT III
Alarm
Set up multi-level alarms
29 multi-level alarms
Power
Operating range
80–265 VAC (maximum power: 4.6 W
)
100–300 VDC
Frequency
Operating frequency
50/60 Hz
Communication
RS-485 port
Modbus-RTU, Modbus ASCII
Baud rate 9600 / 19200 / 38400 bps
Mechanical
Characteristics
Dimension (W x H x D)
96 x 96 x 95.4 mm
IP Degree of Protection
IP20 (Power meter body)
Measurement Accuracy
Power factor
±
0.5 %
Frequency
±
0.5 %
Electrical
Quantity
Voltage/ Current
±
0.5 %
Electric
Energy
Real power
±
0.5 %
Real power/ Reactive power/
Apparent power
±
0.5 %
Reactive power
±
0.5 %
Apparent power
±
2.0 %
Summary of Contents for DPM-D520I
Page 3: ......
Page 9: ...Delta Din rail Power Meter DPM D520I User Manual 1 4 _1 _1 MEMO...
Page 15: ...Delta Din rail Power Meter DPM D520I User Manual 2 6 _2 MEMO...
Page 31: ...Delta Din rail Power Meter DPM D520I User Manual 4 10 _4 MEMO...
Page 116: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Error Codes 6 2 6 2 Alarm Types 6 2 6...
Page 119: ...Delta Din rail Power Meter DPM D520I User Manual 6 4 _6 Memo...
Page 125: ...Delta Din rail Power Meter DPM D520I User Manual A 6 _A _1 _1 MEMO...