Chapter 5 Parameters and Functions
5-17
_5
B9
40186 Alarm enable
0: Disable
1: Enable
word
2
R/W
BA
40187
Pickup setpoint (THD
voltage value
exceeding this value
triggers alarm)
0.000 – 999.999
float
%
4
R/W
BB
40188
BC
40189
Pickup time delay
(alarm–trigger delay) 0 – 99
word
s
2
R/W
BD
40190
Dropout setpoint
(THD voltage value
below this value,
alarm cleared)
0.000 – 999.999
float
%
4
R/W
BE
40191
BF
40192
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W
Alarm – Over THD Current
C0
40193 Alarm enable
0: Disable
1: Enable
word
2
R/W
C1
40194
Pickup setpoint (THD
current value
exceeding this value
triggers alarm)
0.000 – 999.999
float
%
4
R/W
C2
40195
C3
40196
Pickup time delay
(alarm–trigger delay) 0 – 99
word
s
2
R/W
C4
40197
Dropout setpoint
(THD current value
below this value,
alarm cleared)
0.000 – 999.999
float
%
4
R/W
C5
40198
C6
40199
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W
Alarm – Phase Loss
Summary of Contents for DPM-D520I
Page 3: ......
Page 9: ...Delta Din rail Power Meter DPM D520I User Manual 1 4 _1 _1 MEMO...
Page 15: ...Delta Din rail Power Meter DPM D520I User Manual 2 6 _2 MEMO...
Page 31: ...Delta Din rail Power Meter DPM D520I User Manual 4 10 _4 MEMO...
Page 116: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Error Codes 6 2 6 2 Alarm Types 6 2 6...
Page 119: ...Delta Din rail Power Meter DPM D520I User Manual 6 4 _6 Memo...
Page 125: ...Delta Din rail Power Meter DPM D520I User Manual A 6 _A _1 _1 MEMO...