KKER9C02-A0-page 1

  320*340 TFT color LCD display.  

  Measure 3 phase voltage , ampere , reactive power ,active power , apparent power , power factor , frequency , Kwh , KvarH ect.

⊙ 

Three phase voltage , ampere , active power , reactive power ,and other parameters real time record and curve record storage

⊙ 

Total Kwh and total KvarH accumulation memory function

.

  Both side and outside storage  , support SD card and USB storage , maximum storage is 4GB

⊙ 

Switch output:  AL1, AL2 relay switch output 

⊙ 

Analog output : one 4-20mA DC transmition output.

⊙ 

Switch input :4 switch input S1-S4 , used in remote control the electric swith status.

⊙ 

With RS485 communication , Modbus RTU

⊙ 

Optional tariff statistics function, with demand statistics function.

Optional harmonic analysis funtion (including the total harmonics).

⊙ 

Backup data can be opened by PC software to show the real time curve record

Features:

※  

Caution

Warning

2

ER9 Series 3 Phase Multi-function Power Recorder Operation Manual

This meter can measure and record the true value of voltage , ampere , 

active power , reactive power , power factor , Kwh , KvarH ect. It also

can generates various kinds of report forms . The parameters can copy

 to SD card or USB automatically or by manual . 

With RS485 communication port , support modbus RTU. It can be widly 

used in SCADA system and energy management system , power station 

automation system , power grid , estate power monitor , intelligent building ,

intelligent switchboard  and switch cabinet ect

For your safety , please read the content before usage.

Safe Caution

please read the manual carefully before using the meter .

Please comply with the below important points:

Warning An accident may happen if the operation does not comply 

with the instruction.

Notice An operation that does not comply with the instruction may lead

 to product damage.

The instruction of the symbol in the manual is as below:

An accident danger may happen in a special condition.

1. A safety protection equipment must be installed or please contact with 

us for the relative information if the product is used under the circumstance 

such as nuclear control, medical treatment equipment ,automobile, train,

airplane, aviation, entertainment or safety equipment, etc. Otherwise, it may

cause serious loss, fire or person injury.

2. Apanel must be installed, otherwise it may cause creepage (leakage).

3. Do not touch wire connectors when the power is on, otherwise you may

   get an electric shock.

4. Do not dismantle or modify the product, If you have to do so, please 

contact with us first. Otherwise it may cause electric shock and fire.

5. Please check the connection number while you connect the power supply

   wire or input signal, otherwise it may cause fire.

1. This product cannot be used outdoors. Otherwise the working life of the 

product will become shorter, or an electric shock accident may happen.

2. When you connect wire to the power input connector or signal input 

connectors, the moment of the No.20AWG (0.50 mm2) scrwew tweaked 

to the connector is 0.74n.m-0.9n.m. Otherwise the connectors may be

damaged or get fire.

3. Please comply with the rated specifications. Otherwise it may cause fire

 after the working life of the product becomes shorter.

4. Do not use water or oil base cleaner to clean the product. Otherwise it 

may cause electric shock or fire, and damage the product.

5. This product should be avoid working under the circumstance that is 

flammable, explosive, moist, under sunshine, heat radiation and vibration. 

6. In this unit it must not have dust or deposit, otherwise it may cause fire 

or mechanical malfunction.

7. Do not use gasoline, chemical solvent to clean the cover of the product

 because such solvent can damage it. Please use some soft cloth with 

 water or alcohol to clean the plastic cover.

Summary of Contents for ER9 Series

Page 1: ...n may lead to product damage The instruction of the symbol in the manual is as below An accident danger may happen in a special condition 1 A safety protection equipment must be installed or please contact with us for the relative information if the product is used under the circumstance such as nuclear control medical treatment equipment automobile train airplane aviation entertainment or safety ...

Page 2: ...oltage impedance 300KΩ Voltage Accuracy RMS measurement Accuracy 0 5 AC 0 025 5A Current Range Current Overload Continuous 1 2 times Instantaneous 4 times 10S Current Consumption 0 4VA each phase Current impedance 20mΩ Current Accuracy RMS measurement Accuracy 0 5 Energy Active energy accuracy 0 5 Reactive energy accuracy 1 Power Active power Reactive power Apparent power accuracy 0 5 Display TFT ...

Page 3: ...e input voltage is corresponding to the input current they should have the same phase sequence and direction otherwise data and sign error may occur power and energy D The connection mode of meter which is connected to power network should depend on the CT quantity For 2pcs of CT it should be 3 phase 3 wire connection For 3pcs of CT it shoud be 3 phase 4 wire connection E Please pay high attention...

Page 4: ...nstantaneous parameters energy harmonics measurement tariff rate kwh energy record event record and meter setting and display setting in guide pages to move cursor Press to enter subpages accordingly In electrical energy harmonic tariff record and event page press to back to guide page In meter set and display set interface press to guide page interface ...

Page 5: ...ift the page In any pages press to back to guide page In the bottom of display interface there is press key operation remind Energy Interface Operation SET In energy interface press key to shift the page In any pages press to back to guide page In the bottom of display interface there is press key operation remind ...

Page 6: ...age In the bottom of display interface there is press key operation remind In any page press to back to guide page Note This function is not available now SET In tariff interface press key to shift the page In any pages press to back to guide page In the bottom of display interface there is press key operation remind ...

Page 7: ... the page Press to back to guide page In the bottom of display interface there is press key operation remind SET In electrical interface press key to shift the page In any pages press to back to guide page In the bottom of display interface there is press key operation remind 1 realtime curve display operation ...

Page 8: ... box press or to select to delete cancel or modify operation After finishing value modification press to confirm and exit the interface It will appear whether save the dialog box select yes to storage the value and exit to return the operating menu Press to move to password cursor press password press to confirm to enter configuration set interface No class 1 class 2 description range Signal set L...

Page 9: ...unit Transmit output 20mA Transmit output 4mA Trans 1 Trans 2 can be ordered Please refer to table 1 Mode Unit High Low 1 international standard unit K 1000 times standard unit M means1000000 times standard unit Transmit output 20mA Transmit output 4mA Time set time mode Date time time mode 24 hours Tariff Setting tariff start time calibrate Period 1 tariff means tine tariff Peak tariff flat tarif...

Page 10: ...S PFa PFb UcL UL UabL UcH UH UabH Ubc Uca UL Ia Ib Ic I Pa Pb Pc P Qa Uc U Uab Reference table 1 Reference table for alarm output and transmit output No Parameter switch output code low alarm switch output code high alarm transmit output code 4 20mA Ua A phase voltage Ub B phase voltage Uc C phase voltage U phase voltage of A B or C Uab AB line voltage Ubc BC line voltage Uca CA line voltage UL li...

Page 11: ...monthly report form 5 Backup file name present data file serial number 6 Backup the file to USB or SD card 7 Backup progress bar and backup status display SET ESC 1 Confirm USB or SD card connect well with power recorder check the SD card or USB status remind on the status bar 2 Set backup data start time 3 Set backup data finish time 4 Set the backup file content 5 Confirm the file name file name...

Page 12: ... 100 and 0 Each phase power factor low and high limit default setting is 1 and 0 From Data backup start time Data backup end time to Backup file name backup to USB backup to SD backup to USB backup to SD record kwh everyday record kwh every month record kwh everyday record kwh every month number ok number ABC abc piny There are three type modification adjust input parameter edit input parameter se...

Page 13: ...rid easy for check record curve in each grid or layout 4 A phase real time record curve the color is the same with A phase measuring data 5 B phase real time record curve the color is the same with B phase measuring data 6 C phase real time record curve the color is the same with C phase measuring data 1 Display history record interface name data and time 2 Data recall mode recall mode and cursor ...

Page 14: ...qual to 1kwhX voltage transform PT X current transform CT 2 Remote measure and remote control function 4 loops S1 S4 are used to remote measure electric ON OFF status DO1 DO2 function can be used to remote control electric devices When using Do function alarm mode should be setted as 0 otherwise DO1 and DO2 will be as AL1 AL2 output DO1 DO2 function control value is writen via RS485 interface 3 Co...

Reviews: