1
2
3
4
5
6
KKER9C02-A0-page 3
2
1
3
4
5
6
USB port
SD card
SET
ESC
A
B
C
N
24 25 26
28 29
27
23
21 22
20
23
21 22
20
A
B
C
N
Current input via CT
A
B
C
24 25 26
28 29
27
23
21 22
20
23
21 22
20
A
B
C
* *
4
~20mA
NC
DO2
AL2
NO
NC
NO
AC/DC
100
~240V
COM
+
-
DO1
AL1
POWER
Ua
B-
A+
SCOM
S1
S2
S3
S4
RP
AP
GND
Ub
Uc
Un
la
(Ub) (Uc)
(Ua)
lb
lc
lc
lb
la
1
21
11
12
13
14
15
16
18
19
17
22
23
24
25
26
27
28
29
20
10
2
3
4
5
6
7
8
9
Wire Connection
Note: 1. For voltage input connection terminal,bracket terminals (Ua) (Uc) (Ub) shows 3 phase 3 wire connection method,
2. Current input is current input terminal , all the inputs and outputs must be coherent
Model 1: (3pcs CT) 3 phase 4 wire working mode
Model 2: (2pcs CT): 3 phase 3 wire working mode
Current input
Voltage input
Voltage direct input
Voltage input via PT
Current input
Current input via CT
Voltage input
Voltage direct input
Voltage input via PT
Explanation :
A. Voltage input: Input voltage should not be higher than the rated input voltage of meter, otherwise a PT should be used.
B. Current input: Standard rated input current is 5A. A CT should be used when the input current is bigger than 5A. If some other meters are
connected with the same CT , the connection should be serial for all meters.
C. Please make sure that the input voltage is corresponding to the input current, they should have the same phase sequence and direction,
otherwise data and sign error may occur (power and energy).
D. The connection mode of meter which is connected to power network should depend on the CT quantity. For 2pcs of CT, it should be 3 phase
3 wire connection. For 3pcs of CT, it shoud be 3 phase 4 wire connection.
E. Please pay high attention on the difference between 3 phase 3 wire and 3 phase 4 wire connection , becasue wrong connection may lead to
incorrect calculation of power factor, power and energy .
Panel Indication
Set Key
Left Key
In measure interface, energy,harmonics, tariff rate, record, event interface, used to back to
guide page . In setting interface , select the menu or parameter need to be modified, and press
Set key to make confirmation after finishing modification.
move cursor to left: in parameter modifying interface, used to select the menu and modified parameter.
Right Key
page down: in running interface , used to turn to back page.
move cursor to right: in parameter modifying interface, used to select the menu and modified parameter.
page up: in running interface , used to turn to front page.
Decrease Key
parameter modification: used to decrease value in parameter modification interface.
Increase Key
parameter modification: used to increase value in parameter modification interface.
Return Key
In menu operation, it is used to return to previous menu
No. symbol
Name
Function