SM150T User Manual 1.0
Operation
15
GP2 Logger Controller
Up to 6 SM150Ts can connect to a GP2.
Up to 12 can be connected if not using the temperature sensor.
If using more than 9 you need expansion lid
GP2-G5-LID
These details illustrate connection to Channels 1 and 2:
SM150T wire
Colour GP2 terminal
Power 0V
brown
CH1 (PGND)
Power V+
white
CH1 (PWR)
Soil Moisture Signal HI
blue
CH1 (+)
Soil Moisture Signal LO
black
CH1 (-)
Cable shield
green
CH1 (PGND)
Thermopile HI
grey
CH2(+) and CH2(-)
Fit wire link
For configuration details see the
DeltaLINK
software sensor
Info Panel
and
Help
or
the
GP2 User Manual.
Configure each soil moisture channel as sensor type
SM150T
and configure
the temperature channel as sensor type
SM150T Temperature
.