Chapter 11 Description of Parameter Settings
AFE2000 Series
11-93
Content Address
Function
2105H DC-BUS Voltage (UXXX.X)
220EH Display the IGBT temperature of AFE200 power module in
o
C
220FH Display the ambient temperature in
o
C
2210H Analog input status ON/OFF
2211H Analog output status ON/OFF
2213H The corresponding CPU pin status of digital input
2214H The corresponding CPU pin status of digital output
4. Exception
response:
The AC motor drive is expected to return a normal response after receiving command messages
from the master device. The following depicts the conditions when no normal response is replied to
the master device.
The AC motor drive does not receive the messages due to a communication error; thus, the AC
motor drive has no response. The master device will eventually process a timeout condition.
The AC motor drive receives the messages without a communication error, but cannot handle them.
An exception response will be returned to the master device and an error message “CExx” will be
displayed on the keypad of AC motor drive. The xx of “CExx” is a decimal code equal to the
exception code that is described below.
In the exception response, the most significant bit of the original command code is set to 1, and an
exception code which explains the condition that caused the exception is returned.
Example:
ASCII mode:
RTU mode:
STX ‘:’ Address
01H
‘0’ Function
86H
Address
‘1’ Exception
code
02H
‘8’ CRC
CHK
Low
C3H
Function
‘6’ CRC
CHK
High
A1H
‘0’
Exception code
‘2’
‘7’
LRC CHK
‘7’
CR
END
LF
The explanation of exception codes:
Exception code
Explanation
1
Illegal data value:
The data value received in the command message is not available for the
AFE unit.
2
Illegal data address:
The data address received in the command message is not available for
the AC motor drive.
3
Parameters are locked: parameters can’t be changed
4
Parameters can’t be changed during operation
10
Communication time-out.
Response Delay Time
Factory Setting: 2.0
Summary of Contents for AFE075A23A
Page 1: ...5012604300 AFE0 2011 02 15 ...
Page 8: ...Chapter 1 Introduction AFE2000 Series 1 6 Digital Keypad KPC CE01 ...
Page 12: ...Chapter 2 Installation AFE2000 Series 2 10 This page is intentionally left blank ...
Page 22: ...Chapter 5 Control Terminals AFE2000 Series 5 20 This page is intentionally left blank ...
Page 31: ...Chapter 6 Optional Accessories AFE2000 Series 6 29 ...
Page 42: ...Chapter 6 Optional Accessories AFE2000 Series 6 40 This page is intentionally left blank ...
Page 60: ...8 58 This page is intentionally left blank ...
Page 64: ...Chapter 9 Digital Keypad AFE2000 Series 9 62 This page is intentionally left blank ...