Chapter 11 Description of Parameter Settings
AFE2000 Series
11-82
03 Protection Parameters
This parameter can be set during the operation.
Low Voltage Level
Factory
Setting:
180.0/360.0
Settings 230V model:160.0~220.0V
460Vmodel: 320.0~440.0V
This parameter is used to set the Low Voltage Level.
LV
Pr. 06-00
30V(60V)
input voltage
Current Limit (Drive)
Factory Setting: 150
Settings 0~250%
This parameter sets the maximum current limit for AFE2000 at drive status.
Current Limit (Regenerate)
Factory Setting: 150
Settings 0~250%
This parameter sets the maximum current limit for AFE2000 at energy regenerating status.
Phase Lock Frequency Deviation Level
Factory
Setting:
4.00
Settings 0.00~10.00Hz
When AFE2000 detects phase lock frequency attain 47~63Hz and fluctuate within 1Hz for longer
than 300 ms, AFE2000 phase lock is completed.
Phase Lock Frequency Deviation Time
Factory Setting: 150
Settings 0~1000ms
If the frequency detected is greater than the phaselock frequency and greater than the setting in
Pr.03-03 for a time period longer than Pr.03-04, it will output a phase lock errorsignal (PLE).
IGBT Temperature Warning Level
Factory
Setting:
100.0
Settings 0.0~11.0
℃
Summary of Contents for AFE075A23A
Page 1: ...5012604300 AFE0 2011 02 15 ...
Page 8: ...Chapter 1 Introduction AFE2000 Series 1 6 Digital Keypad KPC CE01 ...
Page 12: ...Chapter 2 Installation AFE2000 Series 2 10 This page is intentionally left blank ...
Page 22: ...Chapter 5 Control Terminals AFE2000 Series 5 20 This page is intentionally left blank ...
Page 31: ...Chapter 6 Optional Accessories AFE2000 Series 6 29 ...
Page 42: ...Chapter 6 Optional Accessories AFE2000 Series 6 40 This page is intentionally left blank ...
Page 60: ...8 58 This page is intentionally left blank ...
Page 64: ...Chapter 9 Digital Keypad AFE2000 Series 9 62 This page is intentionally left blank ...