![Delta Electronics AFE075A23A User Manual Download Page 16](http://html.mh-extra.com/html/delta-electronics/afe075a23a/afe075a23a_user-manual_2475447016.webp)
Chapter 4 Main Circuit Terminals
AFE2000 Series
4-14
Main Circuit Terminals
Frame B
R/L1
T/L3
S/L2
POWER
DETECTION
r1/l1
t1/l3
s1/l2
DC-
+
DC+
Main circuit terminals:
R(L1), S(L2), T(L3),
, DC+, DC-
Models
Max. Wire
Gauge
Min. Wire Gauge
Torque
(±10%)
AFE075A23A 6
AWG
(13.3mm
2
)
AFE075A43A 8
AWG
(8.4mm
2
)
AFE150A43A
4 AWG
(21.2mm
2
)
6 AWG (13.3mm
2
)
M5
35kg-cm
(30.4 lb-in.)
(3.434Nm)
UL installations must use 600V, 75
℃
or 90
℃
wire. Use copper wire
only.
DC+ & DC-: must use 1kV Wire.
NOTE
Terminal r1/l1, s1/l2,
t1/l3
:
Wire Gauge
:
20AWG [0.5mm²] ~ 14 AWG [2.1mm²]
Torque: 12 kg-cm [10.4 lb-in.] (1.18Nm) (±10%)
If additional terminal is needed when wiring, please refer to Figure 1 for
additional terminal dimension.
After crimping the wire to the ring lug please apply the UL approved R/C
(YDPU2) heat shrink tubing rate min 600Vac to the terminal. The insulation shall
be all over the live part. Please refer to Figure 2.
Detection wire
Figure 1
Figure 2
Power wire
Figure 1
Figure 2
Summary of Contents for AFE075A23A
Page 1: ...5012604300 AFE0 2011 02 15 ...
Page 8: ...Chapter 1 Introduction AFE2000 Series 1 6 Digital Keypad KPC CE01 ...
Page 12: ...Chapter 2 Installation AFE2000 Series 2 10 This page is intentionally left blank ...
Page 22: ...Chapter 5 Control Terminals AFE2000 Series 5 20 This page is intentionally left blank ...
Page 31: ...Chapter 6 Optional Accessories AFE2000 Series 6 29 ...
Page 42: ...Chapter 6 Optional Accessories AFE2000 Series 6 40 This page is intentionally left blank ...
Page 60: ...8 58 This page is intentionally left blank ...
Page 64: ...Chapter 9 Digital Keypad AFE2000 Series 9 62 This page is intentionally left blank ...