![Delta Electronics AFE075A23A User Manual Download Page 91](http://html.mh-extra.com/html/delta-electronics/afe075a23a/afe075a23a_user-manual_2475447091.webp)
Chapter 11 Description of Parameter Settings
AFE2000 Series
11-89
‘0’ ‘7’
‘0’ ‘0’
‘0’ ‘0’
Number of data
(count by word)
‘2’ ‘0’
‘D’ ‘0’
LRC Check
‘7’
Content of address 2103H
‘0’
CR ‘7’
END
LF
LRC Check
‘1’
CR
END
LF
RTU mode:
Command Message:
Response Message
Address 01H Address 01H
Function 03H Function 03H
21H
Starting data address
02H
Number of data
(count by byte)
04H
00H 17H
Number of data
(count by world)
02H
Content of data
address 2102H
70H
CRC CHK Low
6FH
00H
CRC CHK High
F7H
Content of data
address 2103H
00H
CRC
CHK
Low
FEH
CRC
CHK
High
5CH
06H: single write, write single data to register.
Example: writing data 6000(1770H) to register 0100H. AFE UNIT address is 01H.
ASCII mode:
Command Message:
Response Message
STX ‘:’ STX ‘:’
‘0’ ‘0’
Address
‘1’
Address
‘1’
‘0’ ‘0’
Function
‘6’
Function
‘6’
‘0’ ‘0’
‘1’ ‘1’
‘0’ ‘0’
Data address
‘0’
Data address
‘0’
‘1’ ‘1’
‘7’ ‘7’
‘7’ ‘7’
Data content
‘0’
Data content
‘0’
‘7’ ‘7’
LRC Check
‘1’
LRC Check
‘1’
CR CR
END
LF
END
LF
RTU mode:
Command Message:
Response Message
Address 01H Address 01H
Function 06H Function 06H
01H 01H
Data address
00H
Data address
00H
17H 17H
Data content
70H
Data content
70H
CRC CHK Low
86H
CRC CHK Low
86H
Summary of Contents for AFE075A23A
Page 1: ...5012604300 AFE0 2011 02 15 ...
Page 8: ...Chapter 1 Introduction AFE2000 Series 1 6 Digital Keypad KPC CE01 ...
Page 12: ...Chapter 2 Installation AFE2000 Series 2 10 This page is intentionally left blank ...
Page 22: ...Chapter 5 Control Terminals AFE2000 Series 5 20 This page is intentionally left blank ...
Page 31: ...Chapter 6 Optional Accessories AFE2000 Series 6 29 ...
Page 42: ...Chapter 6 Optional Accessories AFE2000 Series 6 40 This page is intentionally left blank ...
Page 60: ...8 58 This page is intentionally left blank ...
Page 64: ...Chapter 9 Digital Keypad AFE2000 Series 9 62 This page is intentionally left blank ...