10
AWR-MTD2-XE
EN 11/2010
WATER CONNECTIONS
I A
Water content in the system
Size
0011
0025
0031
0041
0051
0061
0091
Minimum water content
l
24
31,5
40
46
65
74
110
Expansion vessel size
Size 0011
0025
0031
0041
0051
0061
0091
Expansion vessel
l
2
2
2
2
2
4
4
Safety valve calibration
Size 0011
0025
0031
0041
0051
0061
0091
Safety valve
bars
6
6
6
6
6
6
6
Factory connections
Installer connections
1
2
12
12
13
14
14
UTILITY
RETURN
UTILITY
OUTLET
9
8
7
16
3
11
T
6
15
16
T
6
F
5
4
2
10
1
1
9
Utility water circuit connection diagram
1 Pressure
gauge
2
Vibration damper joint
3
Shut off valve
4 Calibrating
valve
5 Flow
switch
6 Thermometer
7 Pump
8 Safety
valve
9 Expansion
vessel
10 Wire mesh filter
11 Unit fill/drain valve
12 Temperature
sensor
13 Differential pressure switch
14 Drain / chemical washing valve
15 System
vent
Condensate drain
In heating mode the unit produces a significant quantity of
condensate, which must be suitably drained.
Proceed as follows:
• Connect the unit condensate drain
• Make sure the drain hose has a incline of at least 2 cm/m,
without obstructions or choking.
• Connect the condensate drain hose to a rainwater drain.
Do not connect to the sewage system as odours may be
sucked up if the water in the drain trap evaporates.
• After connecting, check correct drainage of the conden-
sate by pouring water into the pan.
• If necessary, suitably insulate the condensate drain hose.
• Condensate drainage must not cause problems to objects
or people.
• If the outside air temperature is less than 0°C, the conden-
sate may freeze.
The unit comes with frost protection for the condensate col-
lection basin inside the unit.
Use hot wires on the condensate drain hose downstream of
the unit to protect against frost.
FILLING THE SYSTEM
- Before starting to fill, place the unit mains
switch QF1 in the OFF position.
- Before filling, check that the system drain
valve is closed.
- Open all system and terminal air vents.
- Open system shut off valves.
- Start filling by slowly opening the system water fill valve out-
side the unit.
- When water begins to leak out of the terminal air vent valves,
close them and continue filling until the pressure gauge indi-
cates a pressure of 1.5 bar.
The system must be filled
to a pressure of between 1
and 2 bars.
It is recommende
d that this operation be repeated after
the unit has been operating for a number of hours. The
pressure in the system should be checked regularly and
if it drops below 1 bar, the water content should be
topped-up.
Check
the tightness of the joints.
ON
OFF
Summary of Contents for AWR-MTD2-XE
Page 69: ......