INSTALLER CONNECTIONS
24
AWR-MTD2-XE
EN 11/2010
U I A
SA5 Deactivation contact for excess power con-
sumption
The heat pump accepts an external deactivation signal from
contact SA5 if a power consumption management system is
used to disconnect devices based on set priority, thus avoid-
ing activation of the contactor on the power meter.
Configure the contact, selecting the desired function by set-
ting parameter 015D:
Contact closed: heat pump operation not allowed.
Contact open: heat pump operation allowed.
33 34
SA5
33 34
SA5
SA5 Reduced electricity rate contact
Forced refilling of the reserve storage tanks can be activat-
ed based on different electricity rates during the day.
During reduced rate periods, the heat pump can be forced
on so as to heat the domestic hot water or system storage
tank, where fitted.
Configure the contact, selecting the desired function by set-
ting parameter 015D:
Description
Enable the contact as:
0= Reduced electricity rate
1= Stop operation due to excess
power consumption
Menu
Mn01
Parameter
no.
015D
Value to be
set
1
UOM
-
Contact closed: forced operation during the reduced rate
period.
Contact open: heat pump operation at full electricity rate.
During operation at reduced electricity rate, contact closed,
the domestic hot water set point is 50°C, as shown in the
example, with the contact open it’s 47°C.
This allows operation at a higher temperature, within the
unit’s operating limits, exploiting the lower electricity cost.
Description
Enable the contact as:
0= Reduced electricity rate
1= Stop operation due to excess
power consumption
Enable the set point as:
0= Economy
1= Comfort
Set the value of the domestic hot
water ECONOMY set point
Set the value of the domestic hot
water COMFORT set point
Menu
Mn01
Mn00
Mn00
Mn00
Parameter
no.
015D
0015
0022
0023
Value to be
set
0
0
Example
47
Example
50
UOM
-
-
°C
°C