A5 room controller connection
Installation instructions
The room controller must be installed in the best reference
position for temperature control.
Position the room controller as follows:
• around 1.5 metres from the floor, in a part of the room that
allows the sensor to accurately measure the room temper-
ature;
• away from cold air flows, sunlight or other sources of heat.
• leave enough space above the room controller to allow
assembly and removal where necessary.
• If the room controller is removed from its base, it discon-
nects from the power supply and consequently is no
longer operating.
min.
10 cm
Installation procedure
Assembly
• Separate the front from the rear of the terminal using a
screwdriver r
(1)
• Disconnect the 4-pin connector from the front part
(2)
• Remove the cover A1, unscrewing the screw A2
(3)
.
• Fix the controller support to the wall using the holes A3
(4)
. Support hole size and spacing in figure
(5)
.
• Make the electrical connections as shown in the figure
(6)
,
also see the wiring diagram.
A2
A1
A3
A3
E
131
83,5
86
51 52 53 54 55
TxRx -
TxRx +
GND
24 V
AC
GND
A5 room controller terminal block
Installer terminal block
Number of wires
5 shielded
Power supply wire size
0.5 mm
2
Maximum distance
500 m
1
3
6
4
5
2
INSTALLER CONNECTIONS