17
EN 11/2010
AWR-MTD2-XE
INSTALLER CONNECTIONS
I A
B) SUPPLEMENTARY:
the electric heater operates in sup-
plementary heating mode, together with the compressor, to
satisfy the heating load.
Supplementary heating for low outside air temperature
The electric heater is enabled only when the outside tem-
perature is less than the value of parameter 0304, figure 3.
To enable supplementary heating for low outside air temper-
ature set parameter 0303 = 1 and 010G = 0
Electric heater operation reflects the trend in water outlet
temperature, as shown on the graph in figure 4.
Description
Activation electrical heater
0 = Electrical Heater not enabled
1 = Electrical Heater enabled
Type of outlet electric heater oper-
ation
0 = Supplementary
1 = Replacement
Enable boiler
0 = Boiler not enabled
1 = Boiler enabled
Activation with low outside air temperature
0 = Function not enabled
1 = Function enabled
Outside air temperature to enable elec-
tric heater
Minimum outside air temperature for
heat pump operation (make sure the
value set is the same as shown in the
table)
Electric heater delay time (allows the
heat pump to reach steady operation
and thus avoid activating the heater
when not needed)
Integration time to activate outlet elec-
tric heaters
Menu
Mn01
Mn03
Mn03
Mn03
Mn03
Mn03
Mn06
Mn06
Parameter
no
0300
010G
0301
0303
0304
0311
0616
0617
Value to be
set
1*
0
0*
1
Example
-5°C
-15
60
600
UOM
°C
°C
min.
°C*sec
Outlet electric heater control
A) REPLACEMENT:
The electric heater is enabled when
the outside temperature is less than the value of parameter
0304 and the compressor is off, figure 3.
To enable heater activation in REPLACEMENT mode set
parameter 0303 = 1 and 010G = 1.
Electric heater operation reflects the trend in water outlet
temperature, as shown on the graph in figure 4.
If the heat pump shuts down due to an alarm, the electric
heater is activated automatically regardless of the outside
air temperature.
In REPLACEMENT mode the electric heater activation
delay time is ignored, and the device is activated immediate-
ly if necessary.
Outlet electric heater operating parameters in REPLACE-
MENT mode
Outlet electric heater operating parameters in SUPPLE-
MENTARY mode for OUTSIDE AIR TEMP.
Description
Activation electrical heater
0 = Electrical Heater not enabled
1 = Electrical Heater enabled
Type of outlet electric heater oper-
ation
0 = Supplementary
1 = Replacement
Enable boiler
0 = Boiler not enabled
1 = Boiler enabled
Activation with low outside air temperature
0 = Function not enabled
1 = Function enabled
Outside air temperature to enable elec-
tric heater
Integration time to activate outlet elec-
tric heaters
Menu
Mn03
Mn01
Mn03
Mn03
Mn03
Mn06
Parameter
no
0300
010G
0301
0303
0304
0617
Value to be
set
1*
1
0*
1
Example
-5°C
600
UOM
°C
°C*sec
43 44
6
7
230V / 400V
BT9
N
Solution 2
System with heat pump and outlet electric heater WITHOUT
storage tank.
Position probe BT9 on the system outlet pipe.
2
Set the parameters following the sequence described in
the table
Set the parameters following the sequence described in
the table