MEASURING RH IN CONCRETE SLABS IN ACCORDANCE WITH ASTM F-

2170:  

Navigator Pro can be used to measure the RH in a concrete slab in accordance with the ASTM F-

2170 Standard Test Method for Determining Relative Humidity in Concrete Floor Slabs.   

Basic Test Procedure: 

  Drill 5/8-inch hole in concrete to the appropriate depth and remove debris from the holes.  

Insert a CS-2 concrete sleeve into the hole and plug the sleeve with the cap that is provided 

with each sleeve. 

  Wait approximately 72 hours. 

  Remove protective cap from the concrete sleeve and insert the RH/T-S3 humidity sensor into 

the hole.  Wait approximately 1hr to allow the sensor to acclimate to the RH in the hole. 

  Connect one end of the RH/T-C1 cable to the top of meter and the other end to the exposed 

end of the sensor.  Take a RH reading using the RH/TEMP mode of Navigator Pro as 

described on pages 10 and 17. This reading is the RH of the concrete slab. 

TESTING INSULATION: 

 

Set the meter scale

 for PLASTER as described in the Create/Modify a Job section on page 

11.

 

 

To take a reading,

 attach a 21-E electrode with 4” insulated contact pins to the meter.  Push 

the contact pins through the drywall into the insulation behind it. 

 

Press the SELECT button 

and read the moisture content on the meter scale.  The meter 

displays the “relative” moisture level for two seconds. 

TESTING DRYWALL 

 

Set the meter scale

 for Sheetrock® as described in the Create/Modify a Job section on page 

11.

 

 

To take a reading,

 push the contact pins into the Sheetrock® to their full penetration, if 

possible. 

 

Press the SELECT button 

and read the moisture content on the meter scale.  The meter 

displays the %MC for two seconds. 

Summary of Contents for navigator pro

Page 1: ...O MOISTURE MAPPING METER THERMO HYGROMETER Owner s Manual Version 3 01 For Nav Pro Meters starting with Serial 14642 Test Equipment Depot 800 517 8431 99 Washington Street Melrose MA 02176 TestEquipme...

Page 2: ...he Meter to Default Settings In Basic Mode 11 USING THE METER IN ENHANCED MODE 11 Job Definition 11 To Create or Modify A Job 11 12 To Choose Between Residential Commercial 12 To Set the ID Number 13...

Page 3: ...24 25 25 25 26 27 28 TESTING WOOD USING THE 0 100 REFERENCE SCALE TESTING CONCRETE SLABS MEASURING RH IN CONCRETE SLABS TESTING INSULATION TESTING DRYWALL CARE OF YOUR METER WARRANTY 29 APPENDIX A ROO...

Page 4: ...non wood building materials including Plaster and Concrete Scan Mode o 0 300 numerical reference scale Thermo hygrometer RH T S1 sensor included o Measures RH over the range of 0 100 with accuracy of...

Page 5: ...ble options One of the options is always selected and the user can move navigate the selection to any other available option The keypad is aimed at providing navigational control and not at accessing...

Page 6: ...The battery should be replaced immediately If the battery reaches critical levels the meter will refuse to stay on at power up This gradual warning system is intended to provide the user advanced batt...

Page 7: ...the meter upon power up Or Navigator Pro may be used in ENHANCED mode which requires the user to set job definitions and materials for each location within a job The meter also stores each reading in...

Page 8: ...another reading TO SET THE ALARM IN BASIC PIN MODE 1 If you wish to set the alarm to beep after a pre selected MC value is reached use the keys from the MC screen to highlight the ALARM Press the SEL...

Page 9: ...T 70 F Press the SELECT button to get into the TEMPERATURE sub menu 2 To scroll through the temperature settings use the keys to scroll up or down to a higher or lower temperature value Temperature v...

Page 10: ...igher or lower alarm value 4 After you have selected the alarm value use the key to highlight DONE Press SELECT to get back to the MC SCAN screen Note Default alarm setting for SCAN mode is 300 TO TAK...

Page 11: ...mode use the keys to highlight 4 ENHANCED The Main Menu in ENHANCED mode is as follows Setting the meter to enhanced mode requires you to create job definitions and store readings as described below...

Page 12: ...same job number If it is a new job the next screen will allow you to completely define the job To define a job means to choose between residential or commercial allocate a 3 digit job ID number specif...

Page 13: ...orrection is necessary if the wood temperature is outside the range of 50 F 10 C to 90 F 32 C Set the temperature accordingly and the meter will make the correction 1 To change the temperature use the...

Page 14: ...ay now select the material used for each location 1 Press the SELECT key while the cursor highlights that room and the SELECT MATERIAL menu will be displayed 2 Using the keys select the material or sp...

Page 15: ...he alarm sub menu 3 The default status of the alarm is OFF Press the SELECT key to turn it on 4 After the alarm is turned on use the keys to scroll up or down to a higher or lower alarm value 5 After...

Page 16: ...different location by doing the following 1 Use the keys to highlight LOC Press SELECT to get into the LOCATION definition sub menu 2 Use the keys to change the location Note You can only scroll throu...

Page 17: ...00 TO TAKE A PIN READING 1 From the Enhanced Main Menu use the keys to highlight 2 PIN MODE If you are already in the ENHANCED SCAN screen use the keys to highlight GOTO PIN 2 Press the SELECT key to...

Page 18: ...g sure to align the pin out on the DIN connector 1 From the ENHANCED Main Menu use the key to highlight RH T MODE Then press the SELECT key to get into the RH T mode main menu The meter will display t...

Page 19: ...ading in a room using the NEXT key CLEAR MEMORY This option will delete all the readings stored in the meter but will keep the defined job structures and associated locations and areas in tact RESTORE...

Page 20: ...lmhorst Instrument Co Universal Application Program The meter will display Data on the screen and the base unit will alternately turn on a yellow and red LED while data transfer takes place red indica...

Page 21: ...ndividual records cannot be downloaded to the PC The entire storage content is delivered to the PC during a link session SETUP MENU The Setup group of features allows access to the configurable parame...

Page 22: ...en the last key press and backlight shutdown The default setting for this feature is NO where the backlight is completely disabled Backlight shutdown delays are 10 20 30 seconds It is recommended that...

Page 23: ...tures there is a minimum MC limit below that the meter can not read All readings below this lowest limit are displayed as LOW and are not stored These readings are not considered valid readings and ar...

Page 24: ...moisture will move into a hygroscopic wood floor or build up pressure under a non breathing synthetic floor causing delamination Taking a surface reading Drive two hardened steel masonry nails about 3...

Page 25: ...f meter and the other end to the exposed end of the sensor Take a RH reading using the RH TEMP mode of Navigator Pro as described on pages 10 and 17 This reading is the RH of the concrete slab TESTING...

Page 26: ...5 and 1 indicate a borderline situation Readings greater than 1 indicate material that is too wet for painting or wallpaper A reading above 1 also indicates enough moisture present to allow mold grow...

Page 27: ...iod the calibration of the pin less mode may be adversely affected Under these conditions allow the meter to acclimate to the temperature conditions in which it will be used for minimum 1 2 hours or a...

Page 28: ...Blank page...

Page 29: ...n the Care of Your Meter section UNDER NO CIRCUMSTANCES SHALL DELMHORST BE LIABLE FOR ANY INCIDENTAL INDIRECT SPECIAL OR CONSEQUENTIAL DAMAGES OF ANY TYPE WHATSOEVER INCLUDING BUT NOT LIMITED TO LOST...

Page 30: ...BR3 Bedroom 3 13 BR4 Bedroom 4 14 BR5 Bedroom 5 Page 3 15 HLB Hall Floor B 16 HL1 Hall1 17 HL2 Hall2 18 HL3 Hall3 19 DEN Den 20 FR Family Room 21 LAU Laundry Page 4 22 CLT1 Closet 1 23 CLT2 Closet 2 2...

Reviews: