6
4.2
SIMPLIFIED LEARNING PROCEDURE (also see pages 8-10)
1. Verify the initial settings.
2. Program the remote controls (if needed) with the gate stopped (green LED GC turned on) according
to the following:
a) Press the program button P2/RAD for two seconds: the red LED “RAD” lights up.
b) Press the desired button on each transmitter.
c) Press the program button P2/RAD to exit the programming mode.
LEARNING START:
Position the
gates half
open
Yellow LED
flashes
Yellow LED stays on
The two leaves briefly
open
If motors turns in reverse,
invert wires and start
procedure again from
RESET.
The second leaf closes
ATTENTION
If first leaf instead of second leaf
closes, exchange the two motors
and repeat the procedure from
RESET
Pause for 1 second
Within 5 seconds, press
the programming button
P1/SET for 1 second
End of learning
procedure
Adjust trimmers if necessary
ATTENTION
A variation of trimmer “FOR” (speed)
requires the repetition of the learning procedure from
RESET (the manoeuvre time changes)
The two leaves close until
mechanical stop or
electrical limit switches.
Yellow LED switches off
The first leaf closes
RESET:
press and hold
the programming
button P1/SET for
2 seconds
1
3
4
5
8
6
7
2
INITIAL SETTINGS OF THE CONTROL UNIT
1
2
Pause time
(PAU)
Obstacle sensitivity
(OBS)
Leaves delay
(DEL)
TRIMMERS
Obstacle
intervention time
from 0,1 to 3 sec.
Closing delay
from 0 to 15 sec.
Force/speed
(FOR)
OPERATOR MODEL SETTING (pag. 4)
3
The two leaves open
until mechanical stop or
electrical limit switches
9
DIP N.
Description
DIP STATUS
Operation
OFF OFF
Button 1 of the TX enabled
OFF ON
Button 2 of the TX enabled
ON OFF
Button 3 of the TX enabled
1, 2
CHRADIO
ON ON
Button 4 of the TX enabled
OFF
Rapid re-closing disabled
3
FAST
ON
Rapid re-closing enabled
OFF
Lock stroke disabled
4
STRIKE
ON
Lock stroke enabled
OFF
Flashing light fixed
5
LAMP
ON
Flashing light flashing
OFF
OPEN/PAUSE/CLOSE Mode
6
STEP
ON
STEP by STEP mode
OFF
Automatic closing disabled
7
AUTO
ON
Automatic closing enabled
OFF
Safety test disabled
Gate open spy activated
8
PHTEST
ON
Safety test enabled
Gate open spy deactivated