10 

-  opening  stops  when  the  limit  switches  or  the  obstacle  detection  system  intervenes  or  when  the  manoeuvre 
time has elapsed. If other commands are given during opening they will have no effect. 
- with the automation stopped and in automatic pause each time the timer re-starts from zero. 
Once the pause time has elapsed, the closing manoeuvre takes place and the control unit: 
- carries out a 1 second fixed pre-flash 
- drives the two motors with a 2

nd

 motor delay as set on the DEL trimmer 

- drives the motors for one second at reduced speed (softstart) and then at the speed set on the FOR trimmer. 
- if another command is given during closing the control unit commands a complete re-opening. 
- closing stops when the limit switch or the obstacle detection system intervenes or when the manoeuvre time has elapsed. 

ATTENTION:  Maintaining  the  opening  contact  (“STR”  terminal)  closed,  with  a  temporised  relay  for 
example,  the  control  unit  will  command  opening  and  the  automation  will  remain  open  with  automatic 
closing disabled until the contact is re-opened again (Company Function). 

5.5.2 

Step by step mode without automatic closing 

Switch the 

dip-switch 6

 to ON and the 

dip-switch 7

 to OFF. 

The step by step command sequence is OPEN-STOP-CLOSE-STOP 
The opening and closing manoeuvres take place as described in the previous paragraph. 

5.5.3 

Step by step mode with automatic closing 

Switch the 

dip-switch 6

 to ON and the 

dip-switch 7

 to ON. 

The step-step logic is OPEN/STOP/CLOSE/STOP. 
When the opening manoeuvre has been completed and the pause time set on the PAU trimmer has elapsed the 
control  unit  effects  automatic  closing.  If,  when  the  automation  is  closed,  a  radio  command  is  given,  either 
through the “STR” input command or the START pushbutton on the board, the control unit: 
- commands a one second fixed pre-flash 
- drives the two motors without 2

nd

 motor delay if  the 

DEL trimmer is turned fully counter-clockwise

 

with a 

2

nd

 motor delay

 

of  3 seconds for all the other positions of the DEL trimmer 

drives the motors for one second at reduced speed (softstart) and then at the speed set on the FOR trimmer. 

- opening stops when the limit switch or the obstacle detection system intervene or when the manoeuvre time 
has  elapsed  or  with  a  radio  or  manual  command.  In  the  latter  case  the  control  unit  disables  the  automatic 
closing and another command must be given to re-start the manoeuvre. If the automation is completely open, 
once the pause time has elapsed the closing manoeuvre takes place. The control unit: 
- commands a 1 second fixed pre-flash 
- drives the two motors with a 2

nd

 motor delay as set on the DEL trimmer 

- drives the motors for one second at reduced speed (softstart) and then at the speed set on the FOR trimmer. 
- closing stops when the limit switch or the obstacle detection system intervenes or when the manoeuvre time has elapsed. 

5.5.4 

Automatic closing and rapid re-closing mode 

Switch the 

dip-switch 6

 to OFF and the 

dip-switch 7

 to ON. 

Switch the 

dip-switch 3

 to ON. 

The control unit does the following: 
a)  if the photocell is triggered during opening, the control unit continues the opening, and when the photocell is 
cleared effects a STOP followed, after one second, by the re-closure. 
b) 

 

if the photocell is triggered during standby with the gate open, when the photocell is cleared, after one 

second, automatic re-closure occurs. 
c)  if the photocell is triggered during closure, the control unit effects an inversion and, when the photocell is 
cleared, it effects a STOP followed, after one second, by the re-closure.

 

If during the opening cycle or during the pause the photocell is not triggered, the pause time is as set on the 
“PAU” trimmer. 

5.5.5 

OPEN-CLOSE-OPEN mode 

Switch the 

dip-switch 6

 to OFF and the 

dip-switch 7

 to OFF. 

If, when  the  automation  is closed,  a radio  command  is given,  either  through  the “STR”  input  command  or  the 
START pushbutton on the board, the control unit: 
- commands a one second fixed pre-flash 
- drives the two motors without 2

nd

 motor delay if  the 

DEL trimmer is turned fully counter-clockwise

 

with a 

2

nd

 motor delay

 

of  3 seconds for all the other positions of the DEL trimmer 

drives the motors for one second at reduced speed (softstart) and then at the speed set on the FOR trimmer. 

opening stops when the limit switch or the obstacle detection system intervenes or when the manoeuvre time 

has elapsed. If other commands are given during opening they will have no effect. 
When the automation is completely open, to start closing give a radio or manual command and the control unit: 
- commands a 1 second fixed pre-flash 
- drives the two motors with a 2

nd

 motor delay as set on the DEL trimmer 

drives the motors for one second at reduced speed (softstart) and then at the speed set on the FOR trimmer. 

Summary of Contents for SIRIO 3

Page 1: ...his manual that is an integral part of this Kit BAME S r l declines any responsibility in the event current standards in the country of installation are not complied with The symbol CE conforms with E...

Page 2: ...5 2 OPERATION OF THE SAFETY DEVICES 8 5 3 MOTOR SPEED TRIMMER FOR 9 5 4 DELAY BETWEEN MOTORS TRIMMER DEL 9 5 5 OPENING AND CLOSING OPERATING MODE 9 5 6 PEDESTRIAN OPENING FUNCTION 11 5 7 OBSTACLE SEN...

Page 3: ...or start 1 to 60 stand by time adjustment via trimmer 0 1 to 3 0 obstacle detection triggering time adjustment via trimmer Initial settings using dip switches Signalling LEDs 8 Expansion for electric...

Page 4: ...correct connection and operation of all the accessories connected to the terminal board NOTES INITIAL FACTORY SETTINGS If there is no programming the control unit will operate as follows Step step mo...

Page 5: ...ET RF MODULE FUSE 1 A Mains Transformer 230 12VAC for motors 12VDC Transformer 230 20VAC for motors 24VDC MOTOR 12 VDC max 50W 24VDC max 60W PHO and STP inputs must be bridged if not used Flashing lig...

Page 6: ...re from RESET the manoeuvre time changes The two leaves close until mechanical stop or electrical limit switches Yellow LED switches off The first leaf closes RESET press and hold the programming butt...

Page 7: ...rol button 1 The gate closes Will pedestrian function be used Press together P1 SET and P2 RAD Press the button of the remote control that will be used for the pedestrian function different from 1 Con...

Page 8: ...RPA learning pushbutton also see the instructions of the TX used Carry out this operation 5 6 metres from the receiver the LED signals the activation Transmit by pressing one of the channel pushbutto...

Page 9: ...f the motor if 50 of the maximum speed ATTENZION Changing the setting of trimmer FOR requires repeating the learning procedure since the travel times and the slow down start times change EXAMPLE Speed...

Page 10: ...er case the control unit disables the automatic closing and another command must be given to re start the manoeuvre If the automation is completely open once the pause time has elapsed the closing man...

Page 11: ...n of the motion for 2 seconds unless it is in the last five seconds of the manoeuvre where does a STOP 5 8 FLASHING LIGHT The control unit has two output terminals LAMP to command a low voltage flashi...

Page 12: ...l unit is turned on should there be a fault in the EEPROM memory the red LED flashes and all manoeuvres are blocked The Reset function must be executed press and hold the programming button P1 SET for...

Page 13: ...he GTSYSTEM is an autonomous multi functional terminal that can be used on various BAME products both for testing and function modification In the case of SIRIO3 12 24 control unit it allows modificat...

Page 14: ...ery Carry out the remote control acknowledgement procedure Check the lack of mains voltage The flashing light only functions for 4 seconds and the gate moves slowly only with a 12V optional battery fi...

Page 15: ...ce within the times established by the installer the manufacturer and by current legislation All installation maintenance repairs and cleaning operations must be documented This documentation must be...

Page 16: ...MO SEGNATE MN ITALY T el 39 0376 616 638 Fax 39 0376 629 456 http www bame it http www delma it Unit locale Via Enrico Berlinguer 6 63844 GROTTAZZOLINA FM ITALY T el 39 0734 633 533 Fax 39 0734 636 89...

Reviews: