8.  TROUBLESHOOTING 

 

PROBLEM 

PROBABLE CAUSE 

REMEDY 

230 volt mains voltage absent 

Check master switch  

Emergency STOP present 

Check for any STOP commands 
connected to the STP input. 

There is no jumper between the STP 
input and the common. 

If not used, check if there is a 
jumper on the STP input. 

One of the fuses is burnt out. 

Replace the fuse with one of the 
same value. 

On giving a command with the 
remote control or with the key-
switch, the gate

 

does not open

.

 

Motor power cable not connected or 
faulty. 

Check the connection of the cable 
in the terminal board or replace it. 

The photocell, if present, is 
obstructed or not functioning. 

Check, clean the photocell or 
remove the obstacle. 

The photocell is missing and there 
is no jumper between the PHO input 
and the common. 

Check the accessory connections 
and the presence of the “jumper”. 

The gate opens but does not close. 

A key selector NC contact has been 
used instead of an NO contact to 
connect to the STR input  

Check the connections. 

The operator functions by wire but 
not with the remote control. 

The remote control has not been 
memorised or is broken or the 
battery is flat. 

Check/change the battery. 

Carry out the remote control 
acknowledgement procedure. 

Check the lack of mains voltage. 

The flashing light only functions for 
4 seconds and the gate moves 
slowly (only with a 12V optional 
battery fitted). 

No mains voltage: the control unit 
functions with the battery. 

Functioning is normal because it is 
only powered by the battery. 

Check if the leaves are in axis, 
lubricate if necessary. 

Increase the trigger threshold by 
turning the OBS trimmer clockwise. 

The gate moves then stops, both in 
opening and closing. 

The motor force is insufficient 
and/or the trigger threshold of the 
OBS is too low. 

If it is not sufficient, increase the 
FOR trimmer clockwise and 
reprogram from RESET 

Remove any obstacles from the 
gate; restore the hinges, replace or 
lubricate them. 

There is an obstacle in front of the 
gate; the hinges are blocked; a 
motor fixing bracket has detached. 

Check the motor fixings. 

Check the electrical connection. 

Check the correct positioning. 

When commanded, the motor starts 
but the gate does not move. 

The electric lock, if present, does 
not work (does not open). 

Lubricate the mechanism. 

 
 

N.B.: If the problem persists, contact your Retailer or the nearest Service Centre. 
 
ATTENTION: Before sending a remote control to be repaired, check that the batteries are not flat. 50% of 
all remote controls that return for servicing only have flat batteries. 

Summary of Contents for SIRIO 3

Page 1: ...his manual that is an integral part of this Kit BAME S r l declines any responsibility in the event current standards in the country of installation are not complied with The symbol CE conforms with E...

Page 2: ...5 2 OPERATION OF THE SAFETY DEVICES 8 5 3 MOTOR SPEED TRIMMER FOR 9 5 4 DELAY BETWEEN MOTORS TRIMMER DEL 9 5 5 OPENING AND CLOSING OPERATING MODE 9 5 6 PEDESTRIAN OPENING FUNCTION 11 5 7 OBSTACLE SEN...

Page 3: ...or start 1 to 60 stand by time adjustment via trimmer 0 1 to 3 0 obstacle detection triggering time adjustment via trimmer Initial settings using dip switches Signalling LEDs 8 Expansion for electric...

Page 4: ...correct connection and operation of all the accessories connected to the terminal board NOTES INITIAL FACTORY SETTINGS If there is no programming the control unit will operate as follows Step step mo...

Page 5: ...ET RF MODULE FUSE 1 A Mains Transformer 230 12VAC for motors 12VDC Transformer 230 20VAC for motors 24VDC MOTOR 12 VDC max 50W 24VDC max 60W PHO and STP inputs must be bridged if not used Flashing lig...

Page 6: ...re from RESET the manoeuvre time changes The two leaves close until mechanical stop or electrical limit switches Yellow LED switches off The first leaf closes RESET press and hold the programming butt...

Page 7: ...rol button 1 The gate closes Will pedestrian function be used Press together P1 SET and P2 RAD Press the button of the remote control that will be used for the pedestrian function different from 1 Con...

Page 8: ...RPA learning pushbutton also see the instructions of the TX used Carry out this operation 5 6 metres from the receiver the LED signals the activation Transmit by pressing one of the channel pushbutto...

Page 9: ...f the motor if 50 of the maximum speed ATTENZION Changing the setting of trimmer FOR requires repeating the learning procedure since the travel times and the slow down start times change EXAMPLE Speed...

Page 10: ...er case the control unit disables the automatic closing and another command must be given to re start the manoeuvre If the automation is completely open once the pause time has elapsed the closing man...

Page 11: ...n of the motion for 2 seconds unless it is in the last five seconds of the manoeuvre where does a STOP 5 8 FLASHING LIGHT The control unit has two output terminals LAMP to command a low voltage flashi...

Page 12: ...l unit is turned on should there be a fault in the EEPROM memory the red LED flashes and all manoeuvres are blocked The Reset function must be executed press and hold the programming button P1 SET for...

Page 13: ...he GTSYSTEM is an autonomous multi functional terminal that can be used on various BAME products both for testing and function modification In the case of SIRIO3 12 24 control unit it allows modificat...

Page 14: ...ery Carry out the remote control acknowledgement procedure Check the lack of mains voltage The flashing light only functions for 4 seconds and the gate moves slowly only with a 12V optional battery fi...

Page 15: ...ce within the times established by the installer the manufacturer and by current legislation All installation maintenance repairs and cleaning operations must be documented This documentation must be...

Page 16: ...MO SEGNATE MN ITALY T el 39 0376 616 638 Fax 39 0376 629 456 http www bame it http www delma it Unit locale Via Enrico Berlinguer 6 63844 GROTTAZZOLINA FM ITALY T el 39 0734 633 533 Fax 39 0734 636 89...

Reviews: