environmental conditions. Re-mediation of environmental conditions is the responsibility of the
customer.
Table 29. Particulate contamination specifications
Particulate contamination
Specifications
Air filtration
Data center air filtration as defined by ISO Class 8 per ISO
14644-1 with a 95% upper confidence limit.
NOTE: This condition applies to data center
environments only. Air filtration requirements do not
apply to IT equipment designed to be used outside a
data center, in environments such as an office or
factory floor.
NOTE: Air entering the data center must have
MERV11 or MERV13 filtration.
Conductive dust
Air must be free of conductive dust, zinc whiskers, or
other conductive particles.
NOTE: This condition applies to data center and
non-data center environments.
Corrosive dust
• Air must be free of corrosive dust.
• Residual dust present in the air must have a
deliquescent point less than 60% relative humidity.
NOTE: This condition applies to data center and
non-data center environments.
Table 30. Gaseous contamination specifications
Gaseous contamination
Specifications
Copper coupon corrosion rate
<300 Å/month per Class G1 as defined by ANSI/
ISA71.04-1985.
Silver coupon corrosion rate
<200 Å/month as defined by AHSRAE TC9.9.
NOTE: Maximum corrosive contaminant levels measured at ≤50% relative humidity.
Standard operating temperature
Table 31. Standard operating temperature specifications
Standard operating temperature
Specifications
Continuous operation (for altitude less than
950 m or 3117 ft)
10°C to 35°C (50°F to 95°F) with no direct sunlight on the
equipment.
NOTE: The 2.5-inch hard drive chassis supports a
maximum of 145 W processors.
38