9
TrioPure
TM
Sanitation System
DEL Ozone · San Luis Obispo, CA 93401 · USA · 800-676-1335 · Fax: 805-541-8459
2F Electrical
IMPORTANT:
Electrical connections must be made by a
certified electrician. Use copper conductors only. Follow
local and NEC codes. Connect only to a circuit protected by
a Class A GFCI.
Step 1
-
Determine the voltage required for your installation.
Your TrioPure
TM
is configurable for either 120 V or 240 V AC.
Step 2 - For 120 V installations, install the 3.0 A fuse (3A G
type) into the fuse holder. For 240 V installations, install the
1.5 A fuse (3 AG type) into the fuse holder. The fuses are in a
bag attached inside the enclosure near the terminal block.
Warning:
Failure to install the correct fuse voids the warranty
and can present a potential fire and/or electrical hazard.
Step 3 -
Open the front clear cover by opening the latch on
the right side of the enclosure.
Step 4 -
Remove the front panel by pulling off the
Chlorine
Control Knob
and unscrewing four (4) Phillips head 6-32
screws. Locate the terminal block (TB-1).
Figure - 10 Terminal Block 120
V Configurations
Figure - 11 Terminal Block 240
V Configurations
Step 5
- The main power wiring should be routed through 1.5
cm (½”) hole on the left side of the enclosure using appropriate
liquid tight strain relief or conduit (not supplied).
Step 6 -
Connect the main wires to TB-1 as show in
Figure 10
for 120 V installations or
Figure 11
for 240 V installations.
Step 7 -
Connect the local common bonding grid in the area of
the swimming pool, spa or hot tub to the bonding lug (on the
left exterior of the unit) with an insulated or bare solid copper
conductor not smaller than 8 AWG (US) or 6 AWG (Canada).
Step 8 -
Attach the cover plate with the four (4) Phillips head
6-32 screws. Replace the
Chlorine Control Knob
onto the
extended “D” control shaft. Ensure that the ON/OFF switch
is in the “OFF” position. Close and latch the clear cover.
Note:
The TrioPure
TM
must be hard-wired to the AC line side for
24 hour operation to 120 V/60 Hz or 240 V/60 Hz ONLY using
liquid tight fittings/conduit and wire gauges meeting local codes
for the voltage required. Use a permanent marker to indicate
either 120 V or 240 V configuration on the side label found on
the left side of the TrioPure
TM
.
Summary of Contents for TrioPure 25
Page 30: ......