© 2018 | Minimax Fire Protection | 321 Industrial Park Dr. | Hastings, MI 49058 | www.minimax-fire.com

Form No. FX_062098  18.12.04  Rev 18.1

Technical Data Sheet: MX8462-MRI (K5.6) and MX8464-MRI (K8.0) Quick Response Concealed 

Pendent Sprinklers

1.  DESCRIPTION

Quick Response Concealed MRI Sprinklers are intended for use inside an MRI 

environment, such as the MR system room. They are not intended to be used within 

the bore of the MR scanner itself. This sprinkler has been independently tested 

for use with a 3-Tesla MR system in accordance with ASTM F2502-15 criteria. 

The results of this test demonstrate that this product is acceptable for use in an 

environment with a static magnetic field of 3-Tesla or less and the highest spatial 

gradient magnetic field of 330-Gauss/cm or less.

The sprinkler is pre-assembled with a threaded adapter for installation with a low-

profile cover assembly that provides up to ½” (13 mm) of vertical adjustment. The 

two-piece design allows installation and testing of the sprinkler prior to installation 

of the cover plate. The “push-on”, “thread-off” design of the concealed cover plate 

assembly allows easy installation of the cover plate after the system has been tested 

and the ceiling finish has been applied. The cover assembly can be removed and 

reinstalled, allowing temporary removal of ceiling panels without taking the sprinkler 

system out of service or removing the sprinkler.

2.  LISTINGS AND APPROVALS

cULus Listed:

 Category VNIV

*  Refer the Approval Chart and Design Criteria for cULus Listing requirements that must be 

followed.

3.  TECHNICAL DATA

Specifications:

Minimum Operating Pressure: 7 psi (0.5 bar) 

Maximum Working Pressure: 175 psi (12 bar) wwp

Factory tested hydrostatically to 500 psi (34.5 bar)

Thread size: 1/2” (15 mm) NPT or 3/4” (20 mm) NPT

Nominal K-Factor: 5.6 U.S. (80.6 metric**) or 8.0 U.S. (115.2 metric*)

Glass-bulb fluid temperature rated to -65 °F (-55 °C)

Overall Length: 2-1/4” (58 mm)

** Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.

Material Standards - Sprinkler:

Sprinkler Body: Brass UNS-C84400

Deflector: Phosphor Bronze UNS-C51000 

Deflector Pins: Stainless Steel Alloy

Bulb: Glass, nominal 3 mm diameter

Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400

Button: Brass UNS-C36000 

Screws: 18-8 Stainless Steel

Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape

Yoke: Phosphor Bronze UNS-C51000

Cover Adapter: Brass UNS-C26800 

Material Standards - Cover

Cover: Copper UNS-C11000

Base: Brass UNS-C26800 or UNS-C26000

Springs: Nickel Alloy

Solder: Eutectic

Available Temperature Ratings:

Temperature

155 °F (68 °C)

175 °F (79 °C)

200 °F (93 °C)

Suffix

B

D

E

Ordering Information:

 Sprinkler Assembly and Cover Plate must be ordered separately. Refer to Tables 1 and 2.

4.  INSTALLATION

Refer to appropriate NFPA Installation Standards.

5.  OPERATION

During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and 

sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern 

to extinguish or control the fire.

Summary of Contents for MX8462-MRI

Page 1: ...Criteria for cULus Listing requirements that must be followed 3 TECHNICAL DATA Specifications Minimum Operating Pressure 7 psi 0 5 bar Maximum Working Pressure 175 psi 12 bar wwp Factory tested hydrostatically to 500 psi 34 5 bar Thread size 1 2 15 mm NPT or 3 4 20 mm NPT Nominal K Factor 5 6 U S 80 6 metric or 8 0 U S 115 2 metric Glass bulb fluid temperature rated to 65 F 55 C Overall Length 2 1...

Page 2: ...e above 2 Based on NFPA 13 NFPA 13R and NFPA 13D Other limits may apply depending on fire loading sprinkler location and other requirements of the Authority Having Jurisdiction Refer to specific installation standards 3 Requires a 1 2 ratchet which is not available from us TABLE 2 COVER PLATE ORDERING INFORMATION Instructions Using the cover plate base part number 1 add the suffix for the desired ...

Page 3: ...e standard paint colors Listings and approvals apply for any paint manufacturer Contact Minimax Fire Protection for additional information NOTE Custom colors are indicated on a label inside the cover assembly Refer to Figure 1 Design Criteria Also refer to the Approval Chart cULus Listing Requirements Concealed Pendent MRI Sprinklers were subjected to magnetic field interaction testing and determi...

Page 4: ... 2 Sprinkler Installation and Proper Wrench Usage Sprinkler MX8462 Shown NEVER install the sprinkler by applying the installation wrench across the frame arms DO NOT overtighten Use only the designated sprinkler wrenches Minimax Fire Protection Part Numbers 14047WB or 14031 A leak tight seal should be achieved by turning the sprinkler clockwise 1 to 1 1 2 turns beyond finger tight Sprinkler wrench...

Reviews: