INSTALLATION INSTRUCTIONS
Description of parameters
Factory settings
24 MI FF
24 FF
24 MI
24
F01
Type of boiler
10
= sealed chamber
20
= atmospheric chamber
10
10
20
20
F02
Gas used
00
= METHANE
01
= LPG
02
= METHANE (WITH DIAPHRAGM)
02
F03
Hydraulic system
00
= instantaneous appliance
03
= appliance with external storage boiler
04
= appliance for heating only
13
= preheating (24h)
14
= preheating (1h)
13
04
13
04
F04/ F05
Setting programmable relays 1 and 2 (See SERVICE instructions)
00
= no associated function
00
F06
Maximum CH setpoint (°C)
00
= 85°C -
01
= 45°C (function unavailable)
00
F07
DHW inlet priority configuration
00
01
00
01
F08
CH max. output
(0-100%)
100
F09
DHW max. output
(0-100%)
100
F10
Min. heating output
(0-100%)
00
F11
Delay prior to new ignition in CH mode
(00-10 minutes) - 00=10 seconds
03
F12
Diagnostics (See SERVICE Instructions)
--
F13-F14-F15
Factory settings
00
F16
Anti-legionella function
(with F03=03)
00
= disabled
55...67
= enabled (setpoint °C)
00
F17
CH pressure sensor selection
00
= hydraulic pressure sensor
01
= hydraulic differential pressure sensor
00
F18
Manufacture information
00
21. PARAMETER SETTINGS
To set the boiler parameters, press (
–
) and (
–
) together and hold down for at least 6 seconds. When the function is
activate, the “
F01
” appears on the display alternating with the value of the parameter shown.
Edit parameters
• Press (
+/–
) to scroll through the parameters;
• Press (
+/–
) to edit each parameter;
• Press
(
)
, to save the changes. “
MEM
” appears on the display;
• Press
(
i
)
,
to exit without saving. “
ESC
” appears on the display.
22. ADJUSTMENT AND SAFETY DEVICES
The boiler has been designed in full compliance with European reference standards and in particular is fitted with the
following:
• Air pressure switch (model 24 MI FF - 24 FF)
This device only allows the burner to ignite if the exhaust flue duct is in perfect working order.
In the event of one or more of the following faults:
• flue terminal obstructed
• venturi tubes obstructed
• fan blocked
• venturi tube connection - pressure switch tripped
the boiler remains on standby and error code E03 is displayed (see table in section 10).
• Fumes thermostat (model 24 MI - 24)
This device has a sensor positioned on the left section of the fumes hood and shuts off the gas flow to the main burner
if the flue is obstructed and/or if there is no draught.
In these conditions the boiler shuts down and displays error code E03 (section 10).
After eliminating the problem, press button ( ), for at least 2 seconds to re-ignite immediately.
It is forbidden to disable this safety device
Summary of Contents for MS 24
Page 136: ...136 71 03982 03 BG 1 2 3 4 2 3 I 1 0805_2302 CG_2072...
Page 137: ...137 71 03982 03 BG 4 1 3 1 C 1 C 5...
Page 155: ...155 71 03982 03 BG 28 MS 24 MI MS 24 MI FF MS 24 MS 24FF 1 15 15 8 8 29 CG_2284 1009_2405 15...
Page 157: ...157 71 03982 03 BG 16H 16 32 16 CG_2078 1009_2201...
Page 162: ...162 71 03982 03 BG 34 24 MI FF CG_2075 1001_1806 C M N R G V B V NTC NTC...
Page 163: ...163 71 03982 03 BG 24 MI CG_2076 1001_1807 C M N R G V B V NTC NTC...
Page 164: ...164 71 03982 03 BG 24 FF C M N R G V B V M2 NTC CG_2271 1006_1603...
Page 165: ...165 71 03982 03 BG 24 C M N R G V B V M2 NTC CG_2272 1010_2101...
Page 235: ...235 71 03982 03 EL 1 2 3 4 4 2 3 RESET 1 Reset 0805_2302 CG_2072...
Page 236: ...236 71 03982 03 EL 4 1 3 1 C 1 C 5...
Page 251: ...251 71 03982 03 EL 2 3 2 3 2 0 5 bar 180 30 5 C 30 C 25 10 24 10 24 3 bar NTC 23 13 9912070100...
Page 256: ...256 71 03982 03 EL 16H 16 32 16 CG_2078 1009_2201...
Page 261: ...261 71 03982 03 EL 34 24 MI FF CG_2075 1001_1806 C M N R G V B V NTC NTC...
Page 262: ...262 71 03982 03 EL 24 MI CG_2076 1001_1807 NTC NTC C M N R G V B V...
Page 263: ...263 71 03982 03 EL 24 FF M2 NTC CG_2271 1006_1603 C M N R G V B V...
Page 264: ...264 71 03982 03 EL 24 M2 NTC C M N R G V B V CG_2272 1010_2101...
Page 268: ...268 71 03982 03 RU De Dietrich 2 3 1 0805_2302 CG_2072...
Page 269: ...269 71 03982 03 RU 4 5 1 3 1 1 1...
Page 279: ...279 71 03982 03 RU 17 230 3 3x0 75 2 8 9 2 L N L N 1 2 9 CG_2008 1009_0301...
Page 280: ...280 71 03982 03 RU 18 9 1 2 1 2 CG_2260 1006_1501...
Page 285: ...285 71 03982 03 RU 2 3 2 0 5 3 30 5 30 25 10 24 10 24 3 NTC 23 13 9912070100...
Page 286: ...286 71 03982 03 RU 2 2 19 2 2 24 25 1 1009_2401 1009_2402...
Page 288: ...288 71 03982 03 RU 28 MS 24 MI MS 24 MI FF MS 24 MS 24 FF 1 15 15 8 8 29 CG_2284 1009_2405 15...
Page 290: ...290 71 03982 03 RU 16H 16B 32 16 CG_2078 1009_2201...
Page 295: ...295 71 03982 03 RU 34 24 F C N R G V B V NTC NTC CG_2075 1001_1806...
Page 296: ...296 71 03982 03 RU 24 MI C N R G V B V CG_2076 1001_1807 NTC NTC...
Page 297: ...297 71 03982 03 RU 24 FF C N R G V B V CG_2271 1006_1603 2 NTC...
Page 298: ...298 71 03982 03 RU 24 C N R G V B V 2 NTC CG_2272 1010_2101...
Page 302: ...302 71 03982 03 CN 1 2 3 4 2 3 1 0805_2302 CG_2072...
Page 303: ...303 71 03982 03 CN 4 1 30 85 30 45 21 35 60 3 1 C C OFF 5...
Page 318: ...318 71 03982 03 CN 2 3 2 0 5 bar 3 30 5 30 E25 10 24 10 24 3 bar NTC NTC 23 13 9912070100...
Page 323: ...323 71 03982 03 CN 16H 16B 32 0808_2601 CG_2078 16...
Page 328: ...328 71 03982 03 CN 34 24 MI FF C M N R G V B V CG_2075 1001_1806 NTC NTC...
Page 329: ...329 71 03982 03 CN 24 MI CG_2076 1001_1807 C M N R G V B V NTC NTC...
Page 330: ...330 71 03982 03 CN 24 FF C M N R G V B V M2 CG_2271 1006_1603 NTC...
Page 331: ...331 71 03982 03 CN 24 C M N R G V B V M2 NTC CG_2272 1010_2101...