6.4
Controlling a boiler in 0-10 V mode
6.4.1
Electrical connection
Fig.37
Boiler in 0–10 V mode
1
2
3
4
A
ux 1-2 230 V
TA
TS
L
N
T1
T2
L
L
N
N
S1
S2
L
N
MW-3000041-06
34
AVS75
38
+
X40
X41
310
34 Primary pump
38 Remote control with or without room temperature
sensor
310 AVS75: Option
Important
Relay the pumps if the current exceeds 1 A max. per output.
6.4.2
Configuration of the control system
1. Go to the installer parameters.
2. Set the following parameters on the boiler:
Tab.22 Boiler settings in 0–10 V mode
Parameter number
Parameter
Adjustment required
5710
Temps / mode CH1
Off
6020
Function extension module 1
Multifunctional
6046
Function input H2 module 1
Consumer request VK1 10V
6049
Voltage value 1 H2 module 1
0
6050
Funct value 1 H2 module 1
0
6051
Voltage value 2 H2 module 1
6052
Funct value 2 H2 module 1
800
(1) Default setting
(2) This parameter setting is an example. The value 800 means that, at 10 V, the set point will be 80°C.
For more information, see
Modifying the installer parameters, page 70
List of installer parameters, page 76