background image

PSXX Manual Rev: A             Software Rev: F 

17 

 

CV55

 

Block Current Trip Hysteresis

  

  Default = 4. 

  The Block Occupied output will turn ON when the detected current is more than 

the sum of CV54, CV55 and CV56.  

  In general, this value should not be adjusted unless the Block Occupied output is 

chattering on and off.  

CV56 Average Unoccupied Block Current 

  Default = 27, acceptable values 1 - 255. 

  The average value of the current in the block that is just below the trip level.  

  The value may be set manually as required   

  Note: the current input uses a nonlinear function, so manual setting is by trial and 

error) or automatically using CV53.  

  Any current above this value may cause the Block Occupied output to turn ON.  

  When set automatically, a resistance of 3.3K will add enough current above the 

background to turn the Block Occupied output on.  

 

Increasing the value will increase the current required in the block to turn the 

Block Occupied output on. 

 

 

CV63 initiates a PSXX Factory Reset.  

  Using the Program On Main

 

programming mode of your DCC system, set CV63=42.  

  You will see D6 flash. 

   After D6 flashes, all CVs and addresses are returned to their original factory 

values.  

 

The CV63 default is 0. Setting CV63=42 will not change the CV value, but it will 

reset the PSXX. 

 

CV66 

controls how the PSXX outputs power to the track when the associated booster is 

turned on. 

  Default=1 

  CV66=0 The PSXX J2 output will always be OFF after the booster powers up. This 

is useful for staging and storage yards or similar layout sections where there is no 

point in using booster power for equipment that will not be running. When needed, 

the PSXX is turned ON by an Accessory Command.

 

o

  If a photocell is connected and CV50=0, then the photocell will always be 

calibrated and disarmed. It will only control power output.

 

o

  If a photocell is connected and CV50=1, the photocell is enabled to control both 

the PSXX power output and the PSXX Block Occupied output. With this option, 

the photocell remembers its calibration at booster shutdown so that the next 

power on session it will correctly identify if the block is occupied [photocell 

covered] or not [photocell uncovered]. The photocell is NOT calibrated and is 

disarmed

 

o

  If CV50=1, Block Occupied will flash when the photocell is armed. It will become 

steady [on without flashing] when the photocell is covered and the PSXX output 

is switched OFF [stopping train over photocell; Block Occupied indicating 

OCCUPIED].

 

  CV66=1 The PSXX output will always be ON after the booster powers up. 

 

Summary of Contents for PS 1 Series

Page 1: ...t of years of research into problems dealing with false overloads that cause premature shut down of DCC Boosters and other Circuit Breakers These false overloads are caused by large capacitors used in...

Page 2: ...lied to the layout the PSXX can be set to always turn on always remain off power on as needed by DCC command or to use the power status present when the layout was last shut down Outputs for LED Indic...

Page 3: ...t 1 All connections involve two wire inputs from the DCC Booster or Main DCC Power Bus into a PSXX and two wire Outputs to the isolated track block 2 All PSXX circuit breakers are ready to operate wit...

Page 4: ...On Main functions D12 Green LED On indicates DCC power J1 input D7 Green LED On indicates DCC power J2 output D17 Red LED On D7 Green OFF indicates short circuit D18 Blue LED indicates that current li...

Page 5: ...ng more than one PSXX PSXX 2 PSXX 3 insure all input output polarities are the same 3 If you are using a heavier bus wire such as 10 AWG solder a short length of 12 or 14 AWG wire to your heavier bus...

Page 6: ...the PSXX by sending an accessory ON command check your system manual for correct key sequence to accessory address 2042 Refer to CV68 for address limitations c With the Manual Reset jumper in place yo...

Page 7: ...some or all of these trains have more than one locomotive you could have 10 to 15 current drawing units all competing for power in a fairly small area Assuming all the locomotives have efficient moto...

Page 8: ...s is how each district is used In a yard area for example there is a higher risk of derailments occurring with their associated shorts You might want to isolate this area into a separate district so t...

Page 9: ...er Output 2 to track bus JP1 Program Jumper JP1 1 JP1 2 Place jumper on pins 1 2 for Programming JP1 2 JP1 3 Place jumper on pins 2 3 for Operations J4 Block Occupancy J4 1 Input Manual OFF J4 2 GND M...

Page 10: ...pen the switch to reset the PSXX or send an accessory ON command to the PSXX on off command address see Section B item 11 J7 5 TBD J7 6 GND J10 DCC Power In Remote LED Indicator Output J10 1 Remote D1...

Page 11: ...LED The LED is connected directly to the terminals J5 1 and J5 2 have resistors installed on the board that limit the current to about 5mA 780 ohms No resistor is required The remote LED will duplica...

Page 12: ...Accessory Addresses See Section K DCC System Sequential Programming Instructions for Setting Address and Programming CV s The easiest way to address a PSXX circuit breaker is at your workbench The PSX...

Page 13: ...econd address and issue an ON or OFF command 9 Repeat for the third address you want to use 10 Each time you press the ON or OFF key with a new address you should see D17 flash indicating that the PSX...

Page 14: ...he track and the train can be moved Since the photocell is now disarmed you can move the train over the cell without affecting the power status For all systems whenever you enter an address or CV valu...

Page 15: ...unction requires an address 7 Enter the CV number followed by the value The small red LED D17 on the PSXX will blink each time a command is accepted and the CV value is stored correctly in the CV 8 If...

Page 16: ...the solid state switch which allows this connection to be open or closed OFF or ON CV53 Enable Block Current Auto Calibration Default 0 no calibration CV53 66 enables Block Current Auto Calibration th...

Page 17: ...es The CV63 default is 0 Setting CV63 42 will not change the CV value but it will reset the PSXX CV66 controls how the PSXX outputs power to the track when the associated booster is turned on Default...

Page 18: ...the Block Occupied output will flash whenever the photocell is armed The PSXX power output is on The flashing can be inhibited by setting CV67 1 Any other value of CV67 will enable the flashing CV67 d...

Page 19: ...n accessory address you can easily get a feel for the timing involved 5 In normal operating mode not programming mode select an accessory address that has not been programmed into the PSXX 6 Send an a...

Page 20: ...WCH key and switch addresses Digitrax Programming PSXX CVs Using DT400 402 500 Do Setting Addresses First 1 Disconnect PSXX from DCC power 2 Move PSXX JP1 Jumper to Program Position Pins 1 2 3 Turn DC...

Page 21: ...rogram Position Pins 1 2 3 Turn DCC power on 4 Select a locomotive number with the keypad that is unused on your layout 5 Press the F keys and the or key to select POM mode then hit Enter 6 Press or u...

Page 22: ...osition Pins 1 2 3 Turn DCC Power on 4 Use SELECT LOCO to address an unused locomotive number 5 Press PROG ESC key to enter PROGRAM ON MAIN mode 6 Press ENTER to select any unused locomotive number 7...

Page 23: ...rogram Position Pins 1 2 3 Turn DCC Power on 4 Press LOCO to address an unused locomotive number 5 Press PROG key to enter PROG MAIN TRACK mode 6 Press ENTER 7 Continue to press ENTER until CV is in t...

Reviews: