background image

PSXX Manual Rev: A             Software Rev: F 

16 

 

Low Current System Trip Current Settings: 

  For the Digitrax Zephyr [DCS50, DCS51, DCS52], setting values of CV49=01, 

02, & 03 is OK.  

  The NCE Power Cab should use the default value of CV49=02.  

  For the PowerCab cv49=1 is ok too.  

  Most 5 amp boosters should be happy with CV49 = 0-5 

CV50 Block Occupied Detection Method 

  Default = 0. 

  CV50=0 - Block Current controls Block Occupied output.  

  CV50=1 - Photocell controls Block Occupied output.   

  Block current is used to indicate the block is occupied and the train is 

somewhere within the block.   

  Photo cell is used to indicate the train is at a specific point in the block  

CV52 Enable Discrete Control of DCC2 output 

  Default = 0, input is disabled 

  CV52=66 enables discrete on/off control of DCC2 output using J4-1 and J4-2 

inputs.  

  Any other value disables the J4-1 and J4-2 inputs.  

  When enabled, a connection from J4-1 to J4-2 turns DCC2 off. 

  DCC1 is the connection from J1-1 to J2-1. It is a copper trace. DCC2 is the 

connection from J1-2 to J2-2 and goes through the solid state switch which 

allows this connection to be open or closed (OFF or ON).  

CV53

 

Enable Block Current Auto-Calibration

 

  Default = 0, no calibration. 

  CV53=66 enables Block Current Auto-Calibration the next time the PSXX is 

turned on.  

  CV53 is set to 66, power is removed, and JP1 is returned to the 2-3 position. 

  When the PSXX is next turned on, it will measure the average Block Current 

and store the value in CV56.  

  This will prevent the Block Occupied output from turning on due to any 

background current (such as from lights, switch motors, etc.) in the block 

  The Block Occupied will turn on if the current in the block increases above the 

background value due to block occupancy  

  The PSXX automatically returns the value to 0 after the block is calibrated. 

CV54

 

Block Current Off Hysteresis

 sets the current level at which the PSXX turns 

on the Block Occupied output. This allows you to set a level above the leakage 

current on the track to prevent false indications. 

  Default = 5 

  The Block Occupied output will be OFF if the detected current is less than the 

sum of CV56 and CV54.  

  In general, this value should only be adjusted if the Block Occupied output will 

not turn off and you have done an Auto Calibration (see CV53).  

 

 

 

 

Summary of Contents for PS 1 Series

Page 1: ...t of years of research into problems dealing with false overloads that cause premature shut down of DCC Boosters and other Circuit Breakers These false overloads are caused by large capacitors used in...

Page 2: ...lied to the layout the PSXX can be set to always turn on always remain off power on as needed by DCC command or to use the power status present when the layout was last shut down Outputs for LED Indic...

Page 3: ...t 1 All connections involve two wire inputs from the DCC Booster or Main DCC Power Bus into a PSXX and two wire Outputs to the isolated track block 2 All PSXX circuit breakers are ready to operate wit...

Page 4: ...On Main functions D12 Green LED On indicates DCC power J1 input D7 Green LED On indicates DCC power J2 output D17 Red LED On D7 Green OFF indicates short circuit D18 Blue LED indicates that current li...

Page 5: ...ng more than one PSXX PSXX 2 PSXX 3 insure all input output polarities are the same 3 If you are using a heavier bus wire such as 10 AWG solder a short length of 12 or 14 AWG wire to your heavier bus...

Page 6: ...the PSXX by sending an accessory ON command check your system manual for correct key sequence to accessory address 2042 Refer to CV68 for address limitations c With the Manual Reset jumper in place yo...

Page 7: ...some or all of these trains have more than one locomotive you could have 10 to 15 current drawing units all competing for power in a fairly small area Assuming all the locomotives have efficient moto...

Page 8: ...s is how each district is used In a yard area for example there is a higher risk of derailments occurring with their associated shorts You might want to isolate this area into a separate district so t...

Page 9: ...er Output 2 to track bus JP1 Program Jumper JP1 1 JP1 2 Place jumper on pins 1 2 for Programming JP1 2 JP1 3 Place jumper on pins 2 3 for Operations J4 Block Occupancy J4 1 Input Manual OFF J4 2 GND M...

Page 10: ...pen the switch to reset the PSXX or send an accessory ON command to the PSXX on off command address see Section B item 11 J7 5 TBD J7 6 GND J10 DCC Power In Remote LED Indicator Output J10 1 Remote D1...

Page 11: ...LED The LED is connected directly to the terminals J5 1 and J5 2 have resistors installed on the board that limit the current to about 5mA 780 ohms No resistor is required The remote LED will duplica...

Page 12: ...Accessory Addresses See Section K DCC System Sequential Programming Instructions for Setting Address and Programming CV s The easiest way to address a PSXX circuit breaker is at your workbench The PSX...

Page 13: ...econd address and issue an ON or OFF command 9 Repeat for the third address you want to use 10 Each time you press the ON or OFF key with a new address you should see D17 flash indicating that the PSX...

Page 14: ...he track and the train can be moved Since the photocell is now disarmed you can move the train over the cell without affecting the power status For all systems whenever you enter an address or CV valu...

Page 15: ...unction requires an address 7 Enter the CV number followed by the value The small red LED D17 on the PSXX will blink each time a command is accepted and the CV value is stored correctly in the CV 8 If...

Page 16: ...the solid state switch which allows this connection to be open or closed OFF or ON CV53 Enable Block Current Auto Calibration Default 0 no calibration CV53 66 enables Block Current Auto Calibration th...

Page 17: ...es The CV63 default is 0 Setting CV63 42 will not change the CV value but it will reset the PSXX CV66 controls how the PSXX outputs power to the track when the associated booster is turned on Default...

Page 18: ...the Block Occupied output will flash whenever the photocell is armed The PSXX power output is on The flashing can be inhibited by setting CV67 1 Any other value of CV67 will enable the flashing CV67 d...

Page 19: ...n accessory address you can easily get a feel for the timing involved 5 In normal operating mode not programming mode select an accessory address that has not been programmed into the PSXX 6 Send an a...

Page 20: ...WCH key and switch addresses Digitrax Programming PSXX CVs Using DT400 402 500 Do Setting Addresses First 1 Disconnect PSXX from DCC power 2 Move PSXX JP1 Jumper to Program Position Pins 1 2 3 Turn DC...

Page 21: ...rogram Position Pins 1 2 3 Turn DCC power on 4 Select a locomotive number with the keypad that is unused on your layout 5 Press the F keys and the or key to select POM mode then hit Enter 6 Press or u...

Page 22: ...osition Pins 1 2 3 Turn DCC Power on 4 Use SELECT LOCO to address an unused locomotive number 5 Press PROG ESC key to enter PROGRAM ON MAIN mode 6 Press ENTER to select any unused locomotive number 7...

Page 23: ...rogram Position Pins 1 2 3 Turn DCC Power on 4 Press LOCO to address an unused locomotive number 5 Press PROG key to enter PROG MAIN TRACK mode 6 Press ENTER 7 Continue to press ENTER until CV is in t...

Reviews: