Operating instructions
There are also 4 outputs that define the drive’s status:
Alarm
When 1 or more hardware alarms are active in the drive
Ready
When there are no alarms and the motor is in torque (enable active)
End of dispensing
Signal that activates at the end of a predetermined dispensing
Dispensing in progress
Signal that allows you to connect for example a solenoid at the output of the pump (with a
programmable delay)
The drive in the upper part has 2 ethernet ports which are related to a single network interface.
It is possible to insert one or more drives into the PLC network configuration using the supplied
GSDML file. The real time data exchange must be configured in the Drive using the “PROFIdrive
AEC Telegram 500 “ (programmable delay).
This telegram sets up the exchange of 10 INT32 variables for the inputs and 10 INT32 variables for
the outputs (40 + 40 Byte).
INPUT
PIN
DESCRIPTION
OUT 0
13
Alarm
OUT 1
30
Ready
OUT 2
22
End of dispensing
OUT 3
23
Dispensing in progress
5.4 Interfacing via Profinet
AZIONAMENTO POMPE VOLUMETRICHE
PCP
pag
. 23
INGRESSO
PIN
DESCRIZIONE
OUT 0
13
Allarme
OUT 1
30
Ready
OUT 2
22
Fine dosaggio
OUT 3
23
Dosaggio in corso
Interfacciamento via Profinet
Il drive nella parte superiore presente 2 porte ethernet che sono relative ad un’unica
interfaccia di rete. È possibile inserire uno o più drive nella configurazione di rete del
PLC utilizzando il file GSDML fornito. Lo scambio dati real time dovrà essere configurato
nel Drive utilizzando il “PROFIdrive AEC Telegram 500”.
Questo telegramma predispone lo scambio di 10 variabili INT32 per gli ingressi e 10
variabili INT32 per le uscite (40 + 40 Byte).
PLC
input
Variabili
drive
Modbus
Holding
register
Descrizione
Var_1
V111
4-1222
Status
Bit 0 allarme
Bit 1 Ready