PQRM5300 33 Ux Ix xx xx (PS)
20201120-V1
63
7.4.3. Communication interface
7.4.3.1. MODBUS RS485 interface setting
Function
It can be read out through the communication output all of
the measured quantities. The optional communication option
have two operating mode:
•
MODBUS RTU Slave RS485
•
MODBUS ASCII Slave RS485
Sequence of operations
1. Log in the 7. Configurations menu
2. Choose the 7.2. Modul #2 settings menu of the
7. Configurations menu with
/
buttons, and press
the ENTE switch.
Contents this menu depends on device construct.
3. Choose the Protocol menu with
/
buttons, and
press the ENTE switch.
4. Select the protocol, and press OK switch to accept the
new value.
4. Choose the Address menu with
/
buttons, and
press the ENTE switch.
5. Type the MODBUS address of instrument with help
,
- , + switches, and press the OK switch to accept the
value.
6. Choose the Baud rate menu with
/
buttons, and
press the ENTE switch.
7. Select from the menu with
switch the Baud rate
value.
8. Press the SEL switch.
9. Press the OK switch.
10. Choose the Parity menu with
/
buttons, and press
the ENTE switch.
11.Select from the menu with
switch the Parity value.
12. Press the SEL switch.
13. Press the OK switch.
14. Choose the Stop bits menu with
/
buttons, and
press the ENTE switch.
15. Select from the menu with
switch the Stop bit value.
16. Press the SEL switch.
17. Press the OK switch.