PQRM5300 33 Ux Ix xx xx (PS)
80
20201120-V1
7.5. Error LED settings
Function
The error indicator LED is set when the error indication is
enabled in 7.5 Error LED setting menu. The errors are
stored in the memory, and can be viewed in 5. Errors menu.
In 5. Errors menu contain errors states (0 – not occured, 1 -
occured). Errors are cleared after reset.
Sequence of operations
1. Log in the 7. Configuration menu.
2. Choose the 7.5. Error LED setting menu with the
/
buttons, and press ENTER button.
3. In the apperaring menu select and mark or unmark the
error you want to observe, with the
/
/ SEL button.
Attention!
You can mark more then one error!
4. If you want to escape from this menu, press the OK
button.
5. If you want to escape from 7. Configuration menu, press
the BACK button.
Error messages
Error
number:
Explanation:
1
L1 voltage dip
2
L2 voltage dip
3
L3 voltage dip
4
L1 voltage interrupt
5
L2 voltage interrupt
6
L3 voltage interrupt
7
L1 voltage swell
8
L2 voltage swell
9
L3 voltage swell
10
L1 overload
11
L2 overload
12
L3 overload
13
Phase sequence error
14
Frequency out of range
15
Q out of range
16
Modbus communication error
17
Analogue output error
18
Demand overrun
19
Unexpeted syncron signal
20
Missed syncron signal