PQRM5300 33 Ux Ix xx xx (PS)
20201120-V1
53
7.4.1.3.
Digital output,
Limit output settings
Function
Here you can set low limit-, high limit values and hysteresis
and assign them to any measured quantity. The instrument
compares continuously this quantity to the measured value
and activates digital output(s) according the output settings.
Sequence of operations
1. Log in the 7. Configurations menu
2. Choose the 7.2. Modul #1 settings menu of the
7. Configurations menu with
/
buttons, and press
the ENTE switch.
3. Choose the 7.2.1 D1 digital output menu of the 7.2. Modul
#1 settings menu with
/
buttons, and press the
ENTE switch.
4. Select the the Limit signal with
switch, and then
Press the SEL switch.
5. Press the OK switch.
6. Select from the menu with
switch the measured
quantity what you are going to apply the limit function.
7. Press the SEL switch.
8. Press the OK switch.
9. Select from the menu with
switch the limit mode
Signal low limit”
The output changes into active state when measured value
becomes lower as the monitored value.
The output changes into inactive state when measured
value become higher as the monitored value and hysteresis