DT9500
20220103-V2
49
7.10. Display refresh time
(08. menu item)
Function
The instrument performs cca. 15 measurements in each
seconds. It’s too fast to see the changing of the
measurement value.
Here you can define the time periods by which the
instrument displays the new measurement values.
[Default factory setting: 0.5 second]
Sequence of operations
1. Enter the menu by pressing a supervisor code.
The way the code should be type in is described in Chapter
7.1. Type the code in.
You see on the display:
.
2. Keep stepping by pressing the
▲
button as long as you
see this menu item:
.
3. Enter the menu item by pressing the
ENTER
button.
4. You see this
on the display. It’s meaning: 0.5
seconds) The 0.5 numerical value is blinking.
5. Pressing the
▲
button select the time periods by which
the instrument should display the new measurement
values.
•
= once in each 0.5 seconds [Default factory
setting].
•
= once in each 1 second.
•
= once in each 1.5 seconds.
•
= once in each 2 seconds.
•
= once in each 0.1 seconds.
•
= once in each 0.3 seconds.
Summary of Contents for DT9500
Page 1: ...DT9500 Intrinsically Safe Temperature Meter Transmitter Operating Instructions ...
Page 67: ...DT9500 20220103 V2 67 10 2 Application example ...
Page 87: ...DT9500 20220103 V2 87 10 9 ATEX Certification ...
Page 88: ...DT9500 88 20220103 V2 ...
Page 89: ...DT9500 20220103 V2 89 ...
Page 90: ...DT9500 90 20220103 V2 ...
Page 91: ...DT9500 20220103 V2 91 ...
Page 92: ...DT9500 92 20220103 V2 ...
Page 93: ...DT9500 20220103 V2 93 ...
Page 94: ...DT9500 94 20220103 V2 ...
Page 95: ...DT9500 20220103 V2 95 ...
Page 96: ...DT9500 96 20220103 V2 ...
Page 97: ...DT9500 20220103 V2 97 ...
Page 98: ...DT9500 98 20220103 V2 ...
Page 99: ...DT9500 20220103 V2 99 ...
Page 100: ......