The limit output may work in Alarm mode too. This mode is
switched ON by the
parameter. According to the
default factory setting it is switched off (
). When the
Alarm mode is ON (
), the limit output switches on when
it has to switch on according to the measured and
displayed physical value, but it will not switch off even if the
value changes so that it should cause it to switch off. The
output can be switched off by pressing the
ENTER
button
only (acknowledgement).
Alarm mode
Of course, if the condition that causes the output to switch
on persists, the limit output will switch on again when the
ENTER
button is released.
(Similary to working of fire-alarm gear generates fire alarm.
Not suffice to definitive liquidation receipt signal alarming,
but must liquidate fire, generative cause.
After switching on the instrument
After switching on the instrument the limit outputs are
disabled as long as it performs at least three
measurements necessary for a complete averaging. This
takes a few seconds maximum. In this way can be avoid
false signalling due to transients that may appear in the
measuring loop.
Summary of Contents for DT9500
Page 1: ...DT9500 Intrinsically Safe Temperature Meter Transmitter Operating Instructions ...
Page 67: ...DT9500 20220103 V2 67 10 2 Application example ...
Page 87: ...DT9500 20220103 V2 87 10 9 ATEX Certification ...
Page 88: ...DT9500 88 20220103 V2 ...
Page 89: ...DT9500 20220103 V2 89 ...
Page 90: ...DT9500 90 20220103 V2 ...
Page 91: ...DT9500 20220103 V2 91 ...
Page 92: ...DT9500 92 20220103 V2 ...
Page 93: ...DT9500 20220103 V2 93 ...
Page 94: ...DT9500 94 20220103 V2 ...
Page 95: ...DT9500 20220103 V2 95 ...
Page 96: ...DT9500 96 20220103 V2 ...
Page 97: ...DT9500 20220103 V2 97 ...
Page 98: ...DT9500 98 20220103 V2 ...
Page 99: ...DT9500 20220103 V2 99 ...
Page 100: ......