6. The first power on, indicators
6.1. First power on
The instrument is operational immediately after switching on the
power supply (see: previous chapter).
The factory settings are as follows:
•
Input signal source: Pt temperature sensor
•
Wire: 4-wire measurement
•
Average: 10
Input connection points to be connected:
-PI (7), +PI (8), -Pt(9) and +Pt (10)
•
Output type: 4-20 mA passive
•
Error indication: On
•
Analog output scaling, lower value (4 mA): -200 °C
•
Analog output scaling, upper value (20 mA): 800 °C
Output connection points to be connected:
-Iout (5) and +Iout (6).
Before starting normal use, you must setup the instrument as
described in chapter
7. Setting-up
.
Attention!
In the case of incorrect settings or the use of connectors
that are not in accordance with the settings, the instrument will work
incorrectly!