
FUNCTIONS
70 SG4 EXTENDED
Blanking in Advanced Configuration Mode
In ACM a maximum of 5 blanking zones (fixed + floating) can be configured (at least 1
beam of separation between zones is necessary).
In ACM the number of beams can be chosen by the user.
Reduced Resolution
Figure 57 - ACM Configuration
GUI calculates the maximum object size (in mm) that can intercept ESPE without caus-
ing SAFE STATE.
Effective ESPE resolution changes depending on the different value assigned to parame-
ter N.
Safety distance should be calculated according to effective resolution.
1
23 mm
49 mm
2
33 mm
68 mm
3
42 mm
87 mm
4
51 mm
105 mm
VALUE NO.
EFFECTIVE RESOLUTION
ESPE 14 mm
EFFECTIVE RESOLUTION
ESPE 30 mm
Summary of Contents for SG4 FIELDBUS Series
Page 1: ...SG4 Extended INSTRUCTION MANUAL Safety Light Curtains ...
Page 8: ...VIII SG4 EXTENDED COMPLIANCE ...
Page 10: ...X SG4 EXTENDED GENERAL VIEW Figure 1 Safety Light Curtain ...
Page 133: ......
Page 134: ......
Page 135: ......