ENC58 PROG
19
If the encoder is not connected properly and the software tool is not
able to establish a USB connection, then the USB to I2C not found:
check connections!!! warning message appears on the screen.
In such occurrence please check that the USB cable is connected
properly to the USB port and the USB port is working correctly.
It may happen that the interface establishes a proper USB
connection, but it is not able to communicate with the encoder.
In this case the following warning messages appear one after the
other: Reading error of parameters from encoder!!!
Connect again (Disconnected button) and Encoder disconnected!!!
Check encoder connections. When this happens, please check either
the M23 / M12 connectors or the cable wiring in the terminal.
If the software tool is able to connect to the encoder and
communicate properly, but internal errors or faults are found, they will
be indicated by their LEDs lighting red in the diagnostic section of the
page.
Errors are also shown by means of the LEDs in the enclosure of the
encoder; please refer to the section “4.10 Diagnostic LEDs (Figure
1)” on page 11.