Terminating Resistors
Two 121 Ohm, 1% Metal Film, ¼ Watt terminating
resistors should be installed at each side of the DeviceNet
trunk line (not at the end of a drop line or in a node). If the
bus is incorrectly terminated, this can lead to errors in data
transfer or bus failure. Please refer to ODVA
documentation for further details.
Bus Connectors
It is recommended to use only commercially available
DeviceNet connectors for connecting the bus.
When connecting up the C-BOX 4X0, it is recommended to observe the guidelines in
the VDE 0100 regulations for handling electrical equipment.