Manual Datafox ZK-MasterIV
1
11
P16
11
1
P17
vom
TS-TMR33-LTM
zum
TS-TMR33-L
The bus no. is set on 1 via the DIP switch on the
door module without a reader (TS TMR33-TM);
the DIP switch 1 has to be at ON, the DIP switches
2 to 5 have to be at OFF. The DIP switch 7 always
has to be at OFF. Because the module is the last
module in the RS485 bus, the bus with the DIP
switch 8 has to be at ON. The power supply and
the RS485 bus of the TS-TMR33-LTM is connected
analogous to figure
. The power supply for the
external reader is established via PIN 10 and 11 of
the edge connector P16.
Figure 59: TS-TMR33-TM-RS485
RxD (grey) is connected via PIN 2 of the edge connector P17 in figure ... and TxD (yellow) is connected
to PIN 3 of the RS232 stub line.
1
11
P16
11
1
P17
vom
TS-TMR33-TM
The communication with the reader (TS-TMR33-
L) via a RS232 stub line is configured with the DIP
switch 6 at ON. No bus number has to be set for
the reader. The Dip switches 1 -5 are at OFF. The
DIP switch 7 always has to be at OFF. The DIP
switch 8 is also at OFF because no timing has to
be turned on. The power supply of the module is
established via PIN 10 and 11 of the edge connector
P16. The RS485 data channel A is connected via
PIN 3 and the data channel B via PIN 2 of the
edge connector P17.
Figure 60: TS-TMR33-L-RS232-Stich
After setting up and wiring the system, the software configuration has to be done. All tables are manda-
tory. However, the tables holiday and event can be empty. The tables are displayed in the form of text
files. You also can log comments within the text files for an easier maintenance of the system. You only
have to start a comment line with a semicolon in the first column. They must not be configuration data
within this comment line.
Version: 04.01.07.00
Page
83