VLT
®
FCD Series
one frequency converter to another by moving the
LCP control panel. First all parameter values are
copied to the LCP control panel, which can then be
moved to another frequency converter. Here all pa-
rameter values can be copied from the LCP control
unit to the frequency converter.
■
Setup shift
-
Selection of Setup via terminals 29 and 33.
Par. 305
Digital input
=
Selection of Setup, lsb
[31]
Par. 307
Digital input
=
Selection of Setup, msb
[32]
Par. 004
Active setup
=
Multi Setup
[5]
004
004 Active Setup
(ACTIVE SETUP)
Value:
Factory Setup (FACTORY SETUP)
[0]
✭
Setup 1 (SETUP 1)
[1]
Setup 2 (SETUP 2)
[2]
Setup 3 (SETUP 3)
[3]
Setup 4 (SETUP 4)
[4]
Multi Setup (MULTI SETUP)
[5]
Function:
The active parameter Setup is selected here. All pa-
rameters can be programmed in four individual
parameter Setups. Shifts between Setups can be
made in this parameter via a digital input or via se-
rial communication.
Description of choice:
Factory Setup
[0] contains the factory-set parameter
values.
Setup 1-4
[1]-[4] are four individual Setups
which can be selected as required.
Multi Setup
[5] is
used where remote-controlled shifts between the
four Setups via a digital input or via serial communi-
cation is required.
005
005 Programming Setup
(EDIT SETUP)
Value:
Factory Setup (FACTORY SETUP)
[0]
Setup 1 (SETUP 1)
[1]
Setup 2 (SETUP 2)
[2]
Setup 3 (SETUP 3)
[3]
Setup 4 (SETUP 4)
[4]
✭
Active Setup (ACTIVE SETUP)
[5]
Function:
You can select which Setup you want to programme
during operation (applies both via the control panel
and the serial communication port). It is, for exam-
ple, possible to programme
Setup 2
[2], while the
active Setup is set to
Setup 1
[1] in parameter 004
Active Setup
.
Description of choice:
Factory Setup
[0] contains the factory-set data and
can be used as a source of data if the other Setups
are to be reset to a known status.
Setup 1-4
[1]-[4]
are individual Setups that can be programmed freely
during operation. If
Active Setup
[5] is selected, the
programming Setup will be equal to parameter 004
Active Setup
.
NB!:
If data is modified or copied to the active
Setup, the modifications have an immediate
effect on the unit’s operation.
006
006 Setup copying
(SETUP COPY)
Value:
✭
No copying (NO COPY)
[0]
Copy to Setup 1 from #
(COPY TO SETUP 1 )
[1]
Copy to Setup 2 from #
(COPY TO SETUP 2)
[2]
Copy to Setup 3 from #
(COPY TO SETUP 3)
[3]
Copy to Setup 4 from #
(COPY TO SETUP 4)
[4]
Copy to all Setups from # (COPY TO ALL)
[5]
Function:
You can copy from the selected active Setup in pa-
rameter 005
Programming setup
to the selected
Setup or Setups in this parameter.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.04.A1.02 - VLT is a registered Danfoss trade mark
49