VLT
®
FCD Series
■
Mains connection
No. 91 92
93
Mains voltage 3 x 380-480 V
L1
L2
L3
PE
Earth connection
NB!:
Please check that the mains voltage fits
the mains voltage of the frequency converter,
which can be seen from the nameplate.
See
Technical data
for correct dimensioning of cable
cross-section.
■
Pre-fuses
See
Technical data
for correct dimensioning of pre-
fuses.
■
Motor connection
Connect the motor to terminals 96, 97, 98. Connect
earth to PE- terminal.
No. 96
97
98
Motor voltage 0-100% of
mains voltage
U
V
W
3 wires out of motor
U1
W2
V1
U2
W1
V2
6 wires out of motor, Delta
connected
U1 V1
W1 6 wires out of motor, Star con-
nected
U2, V2, W2 to be intercon-
nected separately (optional
terminal block)
PE
Earth connection
See
Technical data
for correct dimensioning of cable
cross-section.
All types of three-phase asynchronous standard mo-
tors can be connected to a frequency converter.
Normally, small motors are star-connected (230/400
V,
1
/ Y). Large motors are delta-connected (400/690
V,
1
/ Y). The correct connection mode and voltage
can be read from the motor nameplate.
NB!:
In motors without phase insulation paper, an
LC filter should be fitted on the output of the
frequency converter.
■
Direction of motor rotation
The factory setting is for clockwise rotation with the
frequency converter transformer output connected
as follows:
Terminal 96 connected to U-phase.
Terminal 97 connected to V-phase.
Terminal 98 connected to W-phase.
The direction of rotation can be changed by switch-
ing two phases on the motor terminals.
■
Parallel connection of motors
MG.04.A1.02 - VLT is a registered Danfoss trade mark
39
Installation