VLT
®
FCD Series
■
Order form
This section makes it easier for you to specify and
order an FCD 300.
Choice of frequency converter
The frequency converter must be chosen on the ba-
sis of the present motor current at maximum loading
of the unit. The frequency converter’s rated output
current I
INV.
must be equal to or greater than the re-
quired motor current.
Mains voltage
FCD 300 is available for mains voltage range: 380-
480 V.
The frequency converter is connected to a mains
voltage of:
-
3 x 380 - 480 V three-phase AC voltage
3 x 380 - 480 Volt mains voltage
Typical shaft output
P
INV.
Max. constant output current
I
INV.
Max. constant output power
at 400 V S
INV.
Type
[kW]
[HP]
[A]
[kVA]
303
0.37
0.50
1.4
1.0
305
0.55
0.75
1.8
1.2
307
0.75
1.0
2.2
1.5
311
1.1
1.5
3.0
2.0
315
1.5
2.0
3.7
2.6
322
2.2
3.0
5.2
3.6
330
3.0
4.0
7.0
4.8
■
Enclosure
All FCD 300 units are supplied with IP 66, NEMA 4x
(Indoor) enclosure as standard.
■
Brake
FCD 300 is available with or without an integral
brake module. See also the section entitled
Brake
resistors
for ordering a brake resistor.
Including mechanical brake control/supply.
■
24 V external supply
Back up of control supply with 24 V DC is available
as optional function.
■
RFI filter
FCD 300 has an integral 1A RFI-filter. The integral
1A RFI filter complies with EMC standards EN
55011-1A. See the sections
Cable lengths
and
Cross section
for further details.
■
Harmonic filter
The harmonic currents do not affect power con-
sumption directly, but they increase the heat losses
in the installation (transformer, cables). That is why
in a system with a relatively high percentage of recti-
fier load it is important to keep the harmonic currents
at a low level so as to avoid a transformer overload
and high cable temperature. For the purpose of en-
suring low harmonic currents, the units are fitted with
coils in their intermediate circuit as standard. This
reduces the input current I
RMS
by typically 40 %.
■
Display unit
On the FCD 300 unit there are 5 indicator lamps for
voltage (ON), warning, alarm, status and bus.
In addition, an LCP control panel to be connected
via a plug to the frequency converter is available as
an option. The LCP control panel can be installed
up to 3 metres away from the frequency converter,
e.g. on a front panel, by means of a mounting kit.
All displays of data are via a 4-line alpha-numerical
display, which in normal operation is able to show 4
operating data items and 3 operation modes continu-