3.2 Applying Power to the Frequency
Converter
WARNING
HIGH VOLTAGE
Frequency converters contain high voltage when
connected to AC mains input power. Only qualified
personnel must perform installation, start-up and
maintenance. Failure to perform installation, start-up and
maintenance by qualified personnel could result in death
or serious injury.
1.
Perform pre-start up procedure described in
.
2.
Confirm input line voltage is balanced within 3%.
If not, correct input voltage imbalance before
proceeding. Repeat procedure after voltage
correction.
3.
Ensure optional equipment wiring, if present,
matches installation application.
4.
Ensure that all operator devices are in OFF
position.
WARNING
UNINTENDED START
When frequency converter is connected to AC mains
input power, the motor may start at any time. The
frequency converter, motor, and any driven equipment
must be in operational readiness. Failure to be in
operational readiness when the frequency converter is
connected to AC mains could result in death, serious
injury, equipment, or property damage.
5.
Apply power to the unit. DO NOT start the
frequency converter at this time. For units with a
disconnect switch on the mains side, turn to the
ON position to apply power to the frequency
converter.
3.3 Quick Setup
Frequency converters require basic operational
programming before running for best performance. Basic
operational programming requires entering motor-
nameplate data for the motor being operated and the
minimum and maximum motor speeds. Enter this data in
accordance with the following procedure. See
, for detailed instructions on
entering data through the LCP. Enter this data with power
ON, but before operating the frequency converter.
1.
Press [Quick Menu] on the LCP.
2.
Use the navigation keys to scroll to parameter
group
Q2 Quick Setup
and press [OK].
130BC394.10
Q1 My Personal Menu
Q2 Quick Setup
Q3 Function Setups
Q5 Changes Made
13.7% 0.75A 1 (1)
Quick Menus
Illustration 3.1 Quick Setup Menu
3.
Select language and press [OK]. Then enter the
motor data in
parameter 1-20 Motor Power [kW]
parameter 1-21 Motor Power [HP]
through
parameter 1-25 Motor Nominal Speed
. The
information can be found on the motor
nameplate. The entire quick menu is shown in
International/North American Default Parameter
Settings
Parameter 1-20 Motor Power [kW]
Parameter 1-21 Motor Power [HP]
Parameter 1-22 Motor Voltage
Parameter 1-23 Motor Frequency
Parameter 1-24 Motor Current
Parameter 1-25 Motor Nominal Speed
130BC395.10
Q2
0.0 Hz
0.00kW
1(1)
Motor Setup
1 - 21 Motor Power [kW]
2.2
kW
Illustration 3.2 Motor Setup Menu
4.
Continue set-up of Quick Menu parameters:
Parameter 5-12 Terminal 27 Digital Input
If terminal default is
Coast inverse
it is
possible to change this setting to
No
function
.
Parameter 1-29 Automatic Motor
Adaptation (AMA)
. Set desired AMA
function. Enable complete AMA is
Start Up and Functional Tes...
Operating Guide
MG04F402