1-23 Motor Frequency
Range:
Function:
Size
related
*
[20 -
1000
Hz]
NOTICE
From software version 6.72 onwards,
the output frequency of the frequency
converter is limited to 590 Hz.
Select the motor frequency value from the
motor nameplate data. If a value other than
50 Hz or 60 Hz is selected, adapt the load-
independent settings in
parameter 1-50 Motor
Magnetisation at Zero Speed
to
parameter 1-53 Model Shift Frequency
. For 87
Hz operation with 230/400 V motors, set the
nameplate data for 230 V/50 Hz. To run at 87
Hz, adapt
parameter 4-13 Motor Speed High
Limit [RPM]
and
1-24 Motor Current
Range:
Function:
Size
related
*
[ 0.10 -
10000.00 A]
NOTICE
This parameter cannot be
adjusted while the motor is
running.
Enter the nominal motor current
value from the motor nameplate data.
The data is used for calculating motor
torque, motor thermal protection, and
so on.
1-25 Motor Nominal Speed
Range:
Function:
Size
related
*
[100 -
60000 RPM]
NOTICE
This parameter cannot be
adjusted while the motor is
running.
Enter the nominal motor speed value
from the motor nameplate data. The
data is used for calculating automatic
motor compensations.
1-29 Automatic Motor Adaptation (AMA)
Option:
Function:
The AMA function optimizes dynamic motor
performance by automatically optimizing the
advanced motor parameters
(
parameter 1-30 Stator Resistance (Rs)
to
parameter 1-35 Main Reactance (Xh)
) at motor
standstill.
Activate the AMA function by pressing [Hand
on] after selecting
[1]
or
[2]
. See also
1-29 Automatic Motor Adaptation (AMA)
Option:
Function:
chapter 3.4 Automatic Motor Adaptation
. After a
normal sequence, the display will read: "Press
[OK] to finish AMA". After pressing [OK] the
frequency converter is ready for operation.
This parameter cannot be adjusted while the
motor is running.
[0]
*
OFF
[1]
Enable
complete
AMA
Performs AMA of the stator resistance R
S
, the
rotor resistance R
r
, the stator leakage reactance
X
1
, the rotor leakage reactance X
2
and the
main reactance X
h
.
[2]
Enable
reduced
AMA
Performs a reduced AMA of the stator
resistance R
s
in the system only. Select this
option if an LC filter is used between the
frequency converter and the motor.
Note:
•
For the best adaptation of the frequency
converter, run AMA on a cold motor.
•
AMA cannot be performed while the motor is
running.
•
AMA cannot be performed on permanent magnet
motors.
NOTICE
It is important to set motor parameter group 1-2*
correctly, since these parameters form part of the AMA
algorithm. An AMA must be performed to achieve
optimum dynamic motor performance. Depending on
the power rating of the motor, It takes up to 10 min.
NOTICE
Avoid generating external torque during AMA, by discon-
necting the motor shaft from the application.
NOTICE
If one of the settings in parameter group 1-2* is
changed,
parameter 1-30 Stator Resistance (Rs)
to
parameter 1-39 Motor Poles
, the Advanced Motor
Parameters return to default setting.
3-02 Minimum Reference
Range:
Function:
Size
related
*
[ -999999.999 -
par. 3-03
ReferenceFeed-
backUnit]
Enter the minimum reference. The
minimum reference is the lowest
value obtainable by summing all
references.
Minimum reference is active only
when
parameter 3-00 Reference Range
is set to
[0] Min.- Max.
The minimum reference unit matches:
Programming
Operating Guide
MG04F402