No. Description
Warning
Alarm/Trip
Alarm/Trip Lock
Parameter Reference
77
Reduced power mode
X
Parameter 14-59 Actual Number of Inverter
Units
78
Tracking Error
(X)
(X)
Parameter 4-34 Tracking Error Function
79
Illegal PS config
X
X
80
Drive Initialized to Default Value
X
81
CSIV corrupt
X
82
CSIV parameter error
X
85
Profibus/Profisafe Error
X
90
Feedback Monitor
(X)
(X)
Parameter 17-61 Feedback Signal
Monitoring
91
Analogue input 54 wrong settings
X
S202
250 New spare part
X
Parameter 14-23 Typecode Setting
251 New Type Code
X
X
Table 7.1 Alarm/Warning Code List
(X) Dependent on parameter
1) Can not be Auto reset via parameter 14-20 Reset Mode
A trip is the action performed when an alarm arises. The trip causes the motor to coast. Reset the trip by pressing [Reset],
or perform a reset via a digital input (parameter group 5-1* [1]). Trip is used when the original event causing the alarm
cannot damage the frequency converter or cause dangerous conditions. A trip lock is the action performed when an alarm
occurs, which can cause damage to the frequency converter or connected parts. A trip lock situation can only be reset by a
power cycling.
LED Indication
Warning
yellow
Alarm
flashing red
Trip locked
yellow and red
Table 7.2 LED Indicator Status