No.
Text
1300
Option SW in slot B is too old.
1315
Option SW in slot A is not supported (not
allowed).
1316
Option SW in slot B is not supported (not
allowed).
1317
Option SW in slot C0 is not supported (not
allowed).
1318
Option SW in slot C1 is not supported (not
allowed).
1379
Option A did not respond when calculating
platform version.
1380
Option B did not respond when calculating
platform version.
1381
Option C0 did not respond when calculating
platform version.
1382
Option C1 did not respond when calculating
platform version.
1536
An exception in the application oriented control is
registered. Debug information written in LCP.
1792
DSP watchdog is active. Debugging of power part
data, motor oriented control data not transferred
correctly.
2049
Power data restarted.
2064-2072 H081x: option in slot x has restarted.
2080-2088 H082x: option in slot x has issued a power-up-
wait.
2096-2104 H983x: option in slot x has issued a legal power-
up-wait.
2304
Could not read any data from power EEPROM.
2305
Missing SW version from power unit
2314
Missing power unit data from power unit
2315
Missing SW version from power unit
2316
Missint lo_statepage from power unit
2324
Power card configuration is determined to be
incorrect at power-up.
2325
A power card has stopped communicating while
main power is applied.
2326
Power card configuration is determined to be
incorrect after the delay for power cards to
register.
2327
Too many power card locations have been
registered as present.
2330
Power size information between the power cards
does not match.
2561
No communication from DSP to ATACD
2562
No communication from ATACD to DSP (state
running)
2816
Stack overflow control board module
2817
Scheduler slow tasks
2818
Fast tasks
2819
Parameter thread
2820
LCP stack overflow
2821
Serial port overflow
2822
USB port overflow
No.
Text
2836
cfListMempool too small
3072-5122 Parameter value is outside its limits.
5123
Option in slot A: Hardware incompatible with
control board hardware.
5124
Option in slot B: Hardware incompatible with
Control board hardware.
5376-6231 Out of memory
Table 9.2 Internal Fault Code Numbers
ALARM 39, Heat sink sensor
No feedback from the heat sink temperature sensor.
The signal from the IGBT thermal sensor is not available on
the power card. The problem could be on the power card,
on the gate drive card, or the ribbon cable between the
power card and gate drive card.
WARNING 40, Overload of digital output terminal 27
Check the load connected to terminal 27 or remove short-
circuit connection. Check
5-00 Digital I/O Mode
and
5-01 Terminal 27 Mode
.
WARNING 41, Overload of digital output terminal 29
Check the load connected to terminal 29 or remove short-
circuit connection. Check
5-00 Digital I/O Mode
and
5-02 Terminal 29 Mode
.
WARNING 42, Overload of digital output on X30/6 or
overload of digital output on X30/7
For X30/6, check the load connected to X30/6 or remove
the short-circuit connection. Check
5-32 Term X30/6 Digi
Out (MCB 101)
.
For X30/7, check the load connected to X30/7 or remove
the short-circuit connection. Check
5-33 Term X30/7 Digi
Out (MCB 101)
.
ALARM 46, Power card supply
The supply on the power card is out of range.
There are 3 power supplies generated by the switch mode
power supply (SMPS) on the power card: 24 V, 5 V, and
±
18 V. When powered with 24 V DC with the MCB 107
option, only the 24 V and 5 V supplies are monitored.
When powered with 3-phase mains voltage, all 3 supplies
are monitored.
WARNING 47, 24 V supply low
The 24 V DC is measured on the control card. The external
24 V DC back-up power supply may be overloaded,
otherwise contact Danfoss.
WARNING 48, 1.8 V supply low
The 1.8 V DC supply used on the control card is outside of
allowable limits. The power supply is measured on the
control card. Check for a defective control card. If an
option card is present, check for an overvoltage condition.
WARNING 49, Speed limit
When the speed is not within the specified range in
4-11 Motor Speed Low Limit [RPM]
and
4-13 Motor Speed
High Limit [RPM]
, the frequency converter shows a warning.
Warnings and Alarms
Operating Instructions
MG16J202
Danfoss A/S © Rev. 05/2014 All rights reserved.
89
9
9
Summary of Contents for VLT FC 103
Page 2: ......