No.
Description
Warning
Alarm/Trip
Alarm/Trip lock
Parameter reference
49
Speed limit
X
(X)
1-86 Trip Speed Low [RPM]
50
AMA calibration failed
X
51
AMA check U
nom
and I
nom
X
52
AMA low I
nom
X
53
AMA motor too big
X
54
AMA motor too small
X
55
AMA Parameter out of range
X
56
AMA interrupted by user
X
57
AMA timeout
X
58
AMA internal fault
X
X
59
Current limit
X
60
External Interlock
X
62
Output Frequency at Maximum Limit
X
64
Voltage Limit
X
65
Control board overtemperature
X
X
X
66
Heat sink Temperature Low
X
67
Option Configuration has Changed
X
68
Safe Stop
1)
(X)
(X)
5-19 Terminal 37 Digital Input
69
Pwr.card temp
X
X
70
Illegal FC configuration
X
77
Reduced Power Mode
79
Illegal PS config
X
X
80
Drive Initialized to Default Value
X
91
Analog input 54 wrong settings
X
92
NoFlow
X
X
22-2* No-Flow Detection
93
Dry Pump
X
X
22-2* No-Flow Detection
94
End of Curve
X
X
22-5* End of Curve
95
Broken Belt
X
X
22-6* Broken Belt Detection
96
Start Delayed
X
22-7* Short Cycle Protection
97
Stop Delayed
X
22-7* Short Cycle Protection
98
Clock Fault
X
0-7* Clock Settings
99
Locked rotor
104
Mixing Fan Fault
X
X
14-53 Fan Monitor
250
New spare parts
X
251
New Type Code
X
X
Table 9.1 Alarm/Warning Code List
(X) Dependent on parameter
1)
Cannot be Auto reset via 14-20 Reset Mode
9.5 Fault Messages
The following warning/alarm information defines each
warning/alarm condition, provides the probable cause for
the condition, and details a remedy or troubleshooting
procedure.
WARNING 1, 10 Volts low
The control card voltage is below 10 V from terminal 50.
Remove some of the load from terminal 50, as the 10 V
supply is overloaded. Max. 15 mA or minimum 590
Ω
.
This condition can be caused by a short in a connected
potentiometer or improper wiring of the potentiometer.
Troubleshooting
•
Remove the wiring from terminal 50. If the
warning clears, the problem is with the customer
wiring. If the warning does not clear, replace the
control card.
WARNING/ALARM 2, Live zero error
This warning or alarm only appears if programmed by the
user in
6-01 Live Zero Timeout Function
. The signal on one
of the analog inputs is less than 50% of the minimum
value programmed for that input. Broken wiring or faulty
device sending the signal can cause this condition.
Warnings and Alarms
Operating Instructions
MG16J202
Danfoss A/S © Rev. 05/2014 All rights reserved.