11.2 General Technical Data
Mains supply (L1, L2, L3)
Supply voltage
380–480 V
±
10%, 525–690 V
±
10%
Mains voltage low/mains voltage drop-out:
During low mains voltage or a mains drop-out, the frequency converter continues until the intermediate circuit voltage drops
below the minimum stop level, which corresponds typically to 15% below the frequency converter's lowest rated supply voltage.
Power-up and full torque cannot be expected at mains voltage lower than 10% below the frequency converter's lowest rated
supply voltage.
Supply frequency
50/60 Hz ±5%
Max. imbalance temporary between mains phases
3.0% of rated supply voltage
True power factor (λ)
≥0.9 nominal at rated load
Displacement power factor (cos Φ) near unity
(>0.98)
Switching on input supply L1, L2, L3 (power ups)
maximum one time/2 min
Environment according to EN60664-1
overvoltage category III/pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100000 RMS symmetrical Amperes, 480/600 V
Motor output (U, V, W)
Output voltage
0-100% of supply voltage
Output frequency
0-590 Hz
1)
Switching on output
Unlimited
Ramp times
0.01-3600 s
1) From software version 1.10 the output frequency of the frequency converter is limited to 590 Hz. Contact local Danfoss partner
for further information.
Torque characteristics
Starting torque (Constant torque)
maximum 110% for 60 s
1)
Starting torque
maximum 135% up to 0.5 s
1)
Overload torque (Constant torque)
maximum 110% for 60 s
1)
1) Percentage relates to the frequency converter's nominal torque
Cable lengths and cross-sections
Max. motor cable length, screened/armoured
150 m
Max. motor cable length, unscreened/unarmoured
300 m
Max. cross section to motor and mains
1)
Maximum cross section to control terminals, rigid wire
1.5 mm
2
/16 AWG (2x0.75 mm
2
)
Maximum cross section to control terminals, flexible cable
1 mm
2
/18 AWG
Maximum cross section to control terminals, cable with enclosed core
0.5 mm
2
/20 AWG
Minimum cross section to control terminals
0.25 mm
2
1) Depending on voltage and power.
Digital inputs
Programmable digital inputs
4 (6)
Terminal number
18, 19, 27
1)
, 29
1)
, 32, 33
Logic
PNP or NPN
Voltage level
0-24 V DC
Voltage level, logic '0' PNP
<5 V DC
Voltage level, logic '1' PNP
>10 V DC
Voltage level, logic '0' NPN
>19 V DC
Voltage level, logic '1' NPN
<14V DC
Maximum voltage on input
28 V DC
Input resistance, R
i
aprrox. 4 kΩ
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1) Terminals 27 and 29 can also be programmed as output.
Specifications
Operating Instructions
98
Danfoss A/S © Rev. 05/2014 All rights reserved.
MG16J202
11
11
Summary of Contents for VLT FC 103
Page 2: ......