2.
Scroll to parameter group
5-1* Digital Inputs
and
press [OK].
130B
T769.10
5-0* Digital I/O mode
5-1* Digital Inputs
5-4* Relays
5-5* Pulse Input
14.7% 0.00A 1(1)
Digital In/Out
5-**
Illustration 6.10 Parameter Group Display Example
3.
Scroll to
5-10 Terminal 18 Digital Input
. Press [OK]
to access function choices. The default setting
Start
is shown.
5-1*
130B
T770.10
5-10 Terminal 18 Digital
Input
[
8
]] Start
14.7% 0.00A 1(1)
Digital Inputs
Illustration 6.11 Function Choice Display Example
6.4 International/North American Default
Parameter Settings
Setting
0-03 Regional Settings
to
[0] International
or
[1]
North America
changes the default settings for some
parameters.
lists those parameters that are
effected.
Parameter
International default
parameter value
North American
default parameter
value
0-03 Regional
Settings
International
North America
0-71 Date Format
DD-MM-YYYY
MM/DD/YYYY
0-72 Time Format
24 h
12 h
1-20 Motor Power
[kW]
See Note 1
See Note 1
1-21 Motor Power
[HP]
See Note 2
See Note 2
1-22 Motor Voltage 230 V/400 V/575 V
208 V/460 V/575 V
1-23 Motor
Frequency
50 Hz
60 Hz
3-03 Maximum
Reference
50 Hz
60 Hz
3-04 Reference
Function
Sum
External/Preset
Parameter
International default
parameter value
North American
default parameter
value
4-13 Motor Speed
High Limit [RPM]
See Note 3
1500 RPM
1800 RPM
4-14 Motor Speed
High Limit [Hz]
See Note 4
50 Hz
60 Hz
4-19 Max Output
Frequency
100 Hz
120 Hz
4-53 Warning Speed
High
1500 RPM
1800 RPM
5-12 Terminal 27
Digital Input
Coast inverse
External interlock
5-40 Function Relay [2] Drive ready
No alarm
6-15 Terminal 53
High Ref./Feedb.
Value
50
60
6-50 Terminal 42
Output
Output frequency
Speed 4-20 mA
14-20 Reset Mode
Manual reset
Infinite auto reset
22-85 Speed at
Design Point [RPM]
See Note 3
1500 RPM
1800 RPM
22-86 Speed at
Design Point [Hz]
50 Hz
60 Hz
Table 6.1 International/North American Default Parameter
Settings
Note 1: 1-20 Motor Power [kW] is only visible when 0-03 Regional
Settings is set to [0] International.
Note 2: 1-21 Motor Power [HP], is only visible when 0-03 Regional
Settings is set to [1] North America.
Note 3: This parameter is only visible when 0-02 Motor Speed Unit is
set to [0] RPM.
Note 4: This parameter is only visible when 0-02 Motor Speed Unit is
set to [1] Hz.
Note 5: The default value depends on the number of motor poles. For
a 4 poled motor, the international default value is 1500 RPM and for
a 2 poled motor, 3000 RPM. The corresponding values for North
America is 1800 and 3600 RPM.
Changes made to default settings are stored and available
for viewing in the Quick Menu along with any
programming entered into parameters.
1.
Press [Quick Menu].
2.
Scroll to
Q5 Changes Made
and press [OK].
3.
Select
Q5-2 Since Factory Setting
to view all
programming changes or
Q5-1 Last 10 Changes
for the most recent.
Programming
Operating Instructions
70
Danfoss A/S © Rev. 05/2014 All rights reserved.
MG16J202
6